Maximum fail-safe mode:
The relay de-energises when the product rises above the upper
switch point: the red LED lights and remains lit until the product
drops below the lower switch point.
Power failure
On power failure both green and red LEDs extinguish: the relay
de-energises.
Level: falling again
Relay:de-energised
Red LED: lit
Level: rising
Relay: energised
Red LED: off
Level: >Max
Relay:de-energised
Red LED: lit
Level: <Min
Relay:energised
Red LED: off
Level
Relay
status
LED
status
Fig. 10
Operational sequence for maximum
fail-safe mode
Power failure
Relay: de-energised
both LEDs: off
Operation