Mounting the Nivotester
The degree of protection of the Nivotester housing is IP 40, that of
the terminals IP 20. Where possible, the units should be mounted
in a switch cabinet or shady position
The limit switches use Minipac housings with snap-on fastenings
suitable for switch cabinet installation on a symmetrical (top hat)
rail. The rail corresponds to EN 50022-35x15 or EN 50022-35x7.5 .
Mount as follows:
Step Procedure
1
Latch the housing on the top of the rail.
2
Push home until the housing snaps on the rail.
Procedure:
Snap-on mounting
Stand-alone installation
The position of installation should be chosen such that the ambient
temperature does not drop below -20 °C or exceed 60 °C
Switching cabinet installation
Fig. 4 is an installation diagram for mounting several units together.
•
The vertical spacing between adjacent rows of units must
exceed 25 mm.
•
Units can be mounted flush with each other provided the ambient
temperature (measured 1 cm above the unit) does not exceed
50 °C.
•
If a gap of 10 mm is left between adjacent units, an ambient
temperature of up to 60° is permissible.
•
The minimum permissible ambient temperature is -20 °C.
25
Top hat rail EN 50022-35x7,5
Fig. 4
Spacing for row or bank mounting
Installation
Nivotester FTC 422
22