LPGmass

Modbus RS485

Coriolis flowmeter

BA01316D/06/EN/01.16

71311937
Valid as of version

01.03.zz (Device firmware)

Содержание MODBUS RS485

Страница 1: ...Products Solutions Services Operating Instructions LPGmass Modbus RS485 Coriolis flowmeter BA01316D 06 EN 01 16 71311937 Valid as of version 01 03 zz Device firmware ...

Страница 2: ...duals or the facility read the Basic safety instructions section carefully as well as all other safety instructions in the document that are specific to working procedures The manufacturer reserves the right to modify technical data without prior notice Your Endress Hauser Sales Center will supply you with current information and updates to these instructions ...

Страница 3: ...19 6 1 3 Special mounting instructions 20 6 2 Mounting the measuring device 20 6 2 1 Required tools 20 6 2 2 Preparing the measuring device 20 6 2 3 Mounting the measuring device 20 6 3 Post installation check 21 7 Electrical connection 22 7 1 Connection conditions 22 7 1 1 Required tools 22 7 1 2 Requirements for connecting cable 22 7 1 3 Terminal assignment 24 7 1 4 Preparing the measuring devic...

Страница 4: ...nostic options 59 12 3 2 Calling up remedy information 61 12 4 Diagnostic information via communication interface 61 12 4 1 Reading out diagnostic information 61 12 4 2 Configuring error response mode 61 12 5 Adapting the diagnostic information 62 12 5 1 Adapting the diagnostic behavior 62 12 6 Overview of diagnostic information 62 12 7 Pending diagnostic events 64 12 8 Diagnostic list 65 12 9 Eve...

Страница 5: ...rious or fatal injury CAUTION CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE NOTE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Electrical symbols Symbol Meaning Direct current Alternating current Direct current and alternating current Ground connection...

Страница 6: ... steps Result of a step Help in the event of a problem Visual inspection 1 2 5 Symbols in graphics Symbol Meaning 1 2 3 Item numbers 1 2 3 Series of steps A B C Views A A B B C C Sections Hazardous area Safe area non hazardous area Flow direction 1 3 Documentation For an overview of the scope of the associated Technical Documentation refer to the following The W M Device Viewer Enter the serial nu...

Страница 7: ...ng and parameterizing the measuring device until the first measured value Product description Installation Electrical connection Operation options System integration Commissioning Diagnostic information Description of Device Parameters Reference for your parameters The document provides a detailed explanation of each individual parameter in the Expert operating menu The description is aimed at tho...

Страница 8: ...labeled accordingly on the nameplate To ensure that the measuring device remains in proper condition for the operation time Only use the measuring device in full compliance with the data on the nameplate and the general conditions listed in the Operating Instructions and supplementary documentation Based on the nameplate check whether the ordered device is permitted for the intended use in the haz...

Страница 9: ...onversions to the device Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers If despite this modifications are required consult with Endress Hauser Repair To ensure continued operational safety and reliability Carry out repairs on the device only if they are expressly permitted Observe federal national regulations pertaining to repair of an electrical d...

Страница 10: ...ass Modbus RS485 10 Endress Hauser IT security measures in line with operators security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves ...

Страница 11: ...d to operate the device One device version is available compact version transmitter and sensor form a mechanical unit 3 1 Product design 3 1 1 Device version with Modbus RS485 communication type 3 2 1 4 A0017609 1 Important components of a measuring device 1 Sensor 2 Transmitter housing 3 Main electronics module 4 Transmitter housing cover In the case of the device version with Modbus RS485 intrin...

Страница 12: ...r code Ser no Ext ord cd i i Date A0029317 Do the nameplate data match the ordering information on the delivery note A0028673 A0029318 Is the CD ROM with the Technical Documentation depends on device version and documents present If one of the conditions is not satisfied contact your Endress Hauser Sales Center Depending on the device version the CD ROM might not be part of the delivery The Techni...

Страница 13: ...ocumentation refer to the following The chapters Additional standard documentation on the device 7 and Supplementary device dependent documentation 7 The W M Device Viewer Enter the serial number from the nameplate www endress com deviceviewer The Endress Hauser Operations App Enter the serial number from the nameplate or scan the 2 D matrix code QR code on the nameplate 4 2 1 Transmitter nameplat...

Страница 14: ... Manufacturing date year month 14 Flow direction 15 2 D matrix code 16 Degree of protection 17 Approval information for explosion protection and Pressure Equipment Directive 18 Permitted ambient temperature Ta 19 Document number of safety related supplementary documentation Order code The measuring device is reordered using the order code Extended order code The device type product root and basic ...

Страница 15: ...ection data e g available inputs and outputs supply voltage 4 Approval information for explosion protection 5 Safety warning 6 Communication specific information 7 Intrinsically safe area 8 Manufacturing location 9 Document number of safety related supplementary documentation 10 Permitted ambient temperature Ta 11 CE mark C Tick 4 2 4 Symbols on measuring device Symbol Meaning WARNING This symbol ...

Страница 16: ...st free place Do not store outdoors Storage temperature 50 to 80 C 58 to 176 F 5 2 Transporting the product Transport the measuring device to the measuring point in the original packaging A0029252 Do not remove protective covers or caps installed on process connections They prevent mechanical damage to the sealing surfaces and contamination in the measuring tube 5 2 1 Measuring devices without lif...

Страница 17: ...orklift 5 3 Packaging disposal All packaging materials are environmentally friendly and 100 recyclable Measuring device secondary packaging polymer stretch film that conforms to EC Directive 2002 95 EC RoHS Packaging Wood crate treated in accordance with ISPM 15 standard which is confirmed by the affixed IPPC logo or Carton in accordance with European Packaging Directive 94 62EC recyclability is c...

Страница 18: ... nameplate helps you to install the sensor according to the flow direction direction of medium flow through the piping Orientation Recommendation A Vertical orientation A0015591 B Horizontal orientation transmitter head up A0015589 1 Exceptions 5 19 C Horizontal orientation transmitter head down A0015590 2 Exceptions 5 19 D Horizontal orientation transmitter head at side A0015592 1 Applications wi...

Страница 19: ...A0029323 Installation dimensions For the dimensions and installation lengths of the device see the Technical Information document Mechanical construction section 6 1 2 Requirements from environment and process Ambient temperature range Measuring device 40 to 60 C 40 to 140 F Safety Barrier Promass 100 40 to 60 C 40 to 140 F If operating outdoors Avoid direct sunlight particularly in warm climatic ...

Страница 20: ...To achieve maximum measuring accuracy even with low flow rates Under extreme process or operating conditions e g very high process temperatures or very high viscosity fluids 6 2 Mounting the measuring device 6 2 1 Required tools For sensor For flanges and other process connections Corresponding mounting tools 6 2 2 Preparing the measuring device 1 Remove all remaining transport packaging 2 Remove ...

Страница 21: ...essure temperature ratings of the Technical Information document Ambient temperature Measuring range Has the correct orientation for the sensor been selected According to sensor type According to medium temperature According to medium properties outgassing with entrained solids Does the arrow on the sensor nameplate match the direction of flow of the fluid through the piping 18 Are the measuring p...

Страница 22: ... connecting cable The connecting cables provided by the customer must fulfill the following requirements Electrical safety In accordance with applicable federal national regulations Permitted temperature range 40 C 40 F to 80 C 176 F Minimum requirement cable temperature range ambient temperature 20 K Power supply cable Standard installation cable is sufficient Signal cable Modbus RS485 The EIA TI...

Страница 23: ...ing device The maximum cable length for individual wire cross sections is specified in the table below Observe the maximum capacitance and inductance per unit length of the cable and the connection values in the Ex documentation Wire cross section Maximum cable length mm2 AWG m ft 0 5 20 70 230 0 75 18 100 328 1 0 17 100 328 1 5 16 200 656 2 5 14 300 984 Cable diameter Cable glands supplied M20 1 ...

Страница 24: ...nals terminals Option B thread M20x1 Option C thread G Option D thread NPT Order code for Housing Option A compact coated aluminum L L 62 72 A B 10 20 _ 1 2 A0030219 6 Modbus RS485 terminal assignment connection version for use in intrinsically safe areas connection via Safety Barrier Promass 100 1 Intrinsically safe power supply 2 Modbus RS485 Order code for Output 20 L 10 L 72 B 62 A Option M In...

Страница 25: ...Remove dummy plug if present 2 If the measuring device is supplied without cable glands Provide suitable cable gland for corresponding connecting cable 3 If the measuring device is supplied with cable glands Observe requirements for connecting cables 22 7 2 Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection Have electrical connection work carried out...

Страница 26: ...age 10 0 4 1 3 mm A0030223 9 Device versions with connection example Engineering unit mm in 1 Cable 1 Loosen the securing clamp of the housing cover 2 Unscrew the housing cover 3 Push the cable through the cable entry To ensure tight sealing do not remove the sealing ring from the cable entry 4 Strip the cable and cable ends In the case of stranded cables also fit ferrules 5 Connect cable in accor...

Страница 27: ...anded cables also fit ferrules 2 Connect the cable in accordance with the terminal assignment 24 3 Where applicable enable the terminating resistor in the Safety Barrier Promass 100 28 2 1 A B 3 A B L L L L A B 5 6 7 4 8 A B L L A0028766 10 Electrical connection between the transmitter and Safety Barrier Promass 100 1 Control system e g PLC 2 Observe cable specifications 22 3 Safety Barrier Promas...

Страница 28: ...ally safe 1 Control system e g PLC 2 Cable shield observe cable specifications 3 Safety Barrier Promass 100 4 Observe cable specifications 5 Non hazardous area 6 Non hazardous area and Zone 2 Div 2 7 Intrinsically safe area 8 Transmitter 7 4 Hardware settings 7 4 1 Enabling the terminating resistor Modbus RS485 To avoid incorrect communication transmission caused by impedance mismatch terminate th...

Страница 29: ... steps after the electrical connection 1 Check that the housing seals are clean and fitted correctly 2 Dry clean or replace the seals if necessary 3 Tighten all housing screws and screw covers 4 Firmly tighten the cable glands 5 To ensure that moisture does not enter the cable entry Route the cable so that it loops down before the cable entry water trap A0029278 6 Insert dummy plugs into unused ca...

Страница 30: ...specifications on the nameplate of the Safety Barrier Promass 100 76 Is the terminal assignment 24 correct If supply voltage is present is the power LED on the electronics module of the transmitter lit green For device version with Modbus RS485 intrinsically safe if supply voltage is present is the power LED on the Safety Barrier Promass 100 lit Depending on the device version is the securing clam...

Страница 31: ...peration options Endress Hauser 31 8 Operation options 8 1 Overview of operating options 1 2 A0017760 1 Computer with FieldCare or DeviceCare operating tool via Commubox FXA291 and service interface 2 Control system e g PLC ...

Страница 32: ...iagnostics Access status display Output Operating menu for experts Language Operatation Language Parameter 1 Setup Submenu 1 Submenu n Device tag Advanced setup Enter access code Parameter 1 Parameter n Submenu 1 Submenu n Diagnostics Parameter 1 Parameter n Submenu 1 Submenu n Operating menu for operators and maintenances Parameter n Operator Maintenance Task oriented Function orien ted Expert Wi...

Страница 33: ...nd device errors Diagnostic list Contains up to 5 currently pending diagnostic messages Event logbook Contains event messages that have occurred Device information Contains information for identifying the device Measured values Contains all current measured values Heartbeat The functionality of the device is checked on demand and the verification results are documented Simulation Is used to simula...

Страница 34: ...ing and saving device data upload download Documentation of the measuring point Visualization of the measured value memory line recorder and event logbook For additional information about FieldCare see Operating Instructions BA00027S and BA00059S Source for device description files See information 36 Establishing a connection 1 Start FieldCare and launch the project 2 In the network Add a device T...

Страница 35: ...ce name 4 Tag name 5 Status area with status signal 60 6 Display area for current measured values 7 Edit toolbar with additional functions such as save restore event list and create documentation 8 Navigation area with operating menu structure 9 Working area 10 Range of action 11 Status area 8 3 3 DeviceCare Function scope Tool to connect and configure Endress Hauser field devices The fastest way ...

Страница 36: ...ntact Endress Hauser 9 2 Modbus RS485 information 9 2 1 Function codes Function codes are used to define which read or write action is carried out via the Modbus protocol The measuring device supports the following function codes Code Name Description Application 03 Read holding register Master reads one or more Modbus registers from the device A maximum of 125 consecutive registers can be read wi...

Страница 37: ...e registers Master reads and writes a maximum of 118 Modbus registers of the measuring device simultaneously with 1 telegram Write access is executed before read access Write and read multiple device parameters Example Read mass flow Reset totalizer Broadcast messages are only allowed with function codes 06 16 and 23 9 2 2 Register information For an overview of device parameters with their respec...

Страница 38: ...e scan list Please note the following basic requirements of the scan list Max entries 16 device parameters Supported device parameters Only parameters with the following characteristics are supported Access type read or write access Data type float or integer Configuring the scan list via FieldCare or DeviceCare Carried out using the operating menu of the measuring device Expert Communication Modb...

Страница 39: ... of scan list register 1 5053 Integer float Read write Value of scan list register Value of scan list register 15 5081 Integer float Read write Data type depends on the device parameters entered in the scan list Data access depends on the device parameters entered in the scan list If the device parameter entered supports read and write access the parameter can also be accessed via the data area ...

Страница 40: ...cal language The operating language can be set in FieldCare or DeviceCare Operation Display language 10 4 Configuring the measuring device The Setup menuwith its submenus contains all the parameters needed for standard operation Setup Device tag 41 System units 41 Medium selection 43 Communication 44 Low flow cut off 46 Partially filled pipe detection 47 10 4 1 Defining the tag name To enable fast...

Страница 41: ...n every device The selection can vary depending on the order code Navigation Setup menu Advanced setup System units System units Mass flow unit 41 Mass unit 41 Volume flow unit 42 Volume unit 42 Corrected volume flow unit 42 Corrected volume unit 42 Density unit 42 Reference density unit 42 Temperature unit 42 Pressure unit 42 Parameter overview with brief description Parameter Description Selecti...

Страница 42: ... unit applies for Output Simulation process variable Density adjustment Expert menu Unit choose list Country specific kg l g cm Reference density unit Select reference density unit Unit choose list Country dependent kg Nl g Scm Temperature unit Select temperature unit Result The selected unit applies for Electronic temperature parameter 6053 Maximum value parameter 6051 Minimum value parameter 605...

Страница 43: ...d submenu contains parameters that must be configured in order to select and set the medium Navigation Setup menu Medium selection Medium selection Select medium 44 Select gas type 44 Reference sound velocity 44 Temperature coefficient sound velocity 44 Pressure compensation 44 Pressure value 44 External pressure 44 ...

Страница 44: ...e Others option is selected Enter sound velocity of gas at 0 C 32 F 1 to 99999 9999 m s 415 0 m s Temperature coefficient sound velocity The Others option is selected in the Select gas type parameter Enter temperature coefficient for the gas sound velocity Positive floating point number 0 m s K Pressure compensation Select pressure compensation type Off Fixed value External value Off Pressure valu...

Страница 45: ...600 BAUD 115200 BAUD 19200 BAUD Data transfer mode Select data transfer mode ASCII RTU RTU Parity Select parity bits Picklist ASCII option 0 Even option 1 Odd option Picklist RTU option 0 Even option 1 Odd option 2 None 1 stop bit option 3 None 2 stop bits option Even Byte order Select byte transmission sequence 0 1 2 3 3 2 1 0 1 0 3 2 2 3 0 1 1 0 3 2 Assign diagnostic behavior Select diagnostic b...

Страница 46: ...Mass flow Volume flow Corrected volume flow Mass flow On value low flow cutoff One of the following options is selected in the Assign process variable parameter 46 Mass flow Volume flow Corrected volume flow Enter on value for low flow cut off Positive floating point number Depends on country and nominal diameter Off value low flow cutoff One of the following options is selected in the Assign proc...

Страница 47: ...Off Density Reference density Off Low value partial filled pipe detection One of the following options is selected in the Assign process variable parameter 47 Density Reference density Enter lower limit value for deactivating partialy filled pipe detection Signed floating point number Country specific 200 kg m3 12 5 lb ft3 High value partial filled pipe detection One of the following options is se...

Страница 48: ...up Advanced setup Enter access code Calculated values 48 Sensor adjustment 49 Totalizer 1 to n 50 Administration 51 10 5 1 Calculated values The Calculated values submenu contains parameters for calculating the corrected volume flow Navigation Setup menu Advanced setup Calculated values Calculated values Corrected volume flow calculation Corrected volume flow calculation 49 External reference dens...

Страница 49: ...e for calculating the reference density 273 15 to 99999 C Country specific 20 C 68 F Linear expansion coefficient In the Corrected volume flow calculation parameter the Calculated reference density option is selected Enter linear medium specific expansion coefficient for calculating the reference density Signed floating point number 0 0 Square expansion coefficient In the Corrected volume flow cal...

Страница 50: ...tures or very high viscosity fluids Navigation Setup menu Advanced setup Sensor adjustment Zero point adjustment Zero point adjustment Zero point adjustment control 50 Progress 50 Parameter overview with brief description Parameter Description Selection User interface Factory setting Zero point adjustment control Start zero point adjustment Cancel Busy Zero point adjust failure Start Cancel Progre...

Страница 51: ...ess variable parameter 51 of the Totalizer 1 to n submenu Select corrected volume unit Unit choose list Country specific Nl Sft 10 5 4 Using parameters for device administration The Administration submenu systematically guides the user through all the parameters that can be used for device administration purposes Navigation Setup menu Advanced setup Administration Administration Device reset 51 Pa...

Страница 52: ... the simulation value for the selected process variable Depends on the process variable selected 0 Simulation device alarm Switch the device alarm on and off Off On Off 10 7 Protecting settings from unauthorized access The following options exist for protecting the configuration of the measuring device from unintentional modification after commissioning Write protection via write protection switch...

Страница 53: ...e On position enables hardware write protection Setting the write protection switch on the main electronics module to the Off position factory setting disables hardware write protection If hardware write protection is enabled the Locking status parameter displays the Hardware locked option if disabled the Locking status parameter does not display any option 4 Reverse the removal procedure to reass...

Страница 54: ...a upload download reset etc Once the internal processing has been completed the parameters can be changed once again 11 2 Adjusting the operating language Detailed information To configure the operating language 40 For information on the operating languages supported by the measuring device 84 11 3 Reading measured values With the Measured values submenu it is possible to read all the measured val...

Страница 55: ...rom the Corrected volume flow unit parameter 42 Signed floating point number Density Shows the density currently measured Dependency The unit is taken from the Density unit parameter 42 Signed floating point number Reference density Displays the reference density currently calculated Dependency The unit is taken from the Reference density unit parameter 42 Signed floating point number Temperature ...

Страница 56: ... number Totalizer overflow One of the following options is selected in the Assign process variable parameter 51 Totalizer 1 to n submenu Volume flow Mass flow Corrected volume flow Displays the current totalizer overflow Integer with sign 11 4 Adapting the measuring device to the process conditions The following are available for this purpose Basic settings using theSetup menu 40 Advanced settings...

Страница 57: ...n Mass flow unit parameter Corrected volume flow option Corrected volume unit parameter Signed floating point number Country specific 0 kg 0 lb Reset all totalizers Reset all totalizers to 0 and start Cancel Reset totalize Cancel 11 5 1 Function scope of the Control Totalizer parameter Options Description Totalize The totalizer is started or continues running Reset hold The totaling process is sto...

Страница 58: ...cs module to the Off position 52 No connection via Modbus RS485 Modbus RS485 bus cable connected incorrectly Check terminal assignment 24 No connection via Modbus RS485 Modbus RS485 cable incorrectly terminated Check terminating resistor 28 No connection via Modbus RS485 Incorrect settings for the communication interface Check the Modbus RS485 configuration 44 No connection via service interface I...

Страница 59: ...ication Flashing white Modbus RS485 communication is active 12 2 2 Safety Barrier Promass 100 Various light emitting diodes LEDs on the Safety Barrier Promass 100 provide status information LED Color Color Power Off Supply voltage is off or too low Green Supply voltage is ok Communication Flashing white Modbus RS485 communication is active 12 3 Diagnostic information in DeviceCare or FieldCare 12 ...

Страница 60: ...rred can be shown in the Diagnostics menu Via parameter Via submenu 65 Status signals The status signals provide information on the state and reliability of the device by categorizing the cause of the diagnostic information diagnostic event Symbol Meaning Failure A device error has occurred The measured value is no longer valid Function check The device is in service mode e g during a simulation O...

Страница 61: ... the Diagnostics menu 1 Call up the desired parameter 2 On the right in the working area mouse over the parameter A tool tip with remedy information for the diagnostic event appears 12 4 Diagnostic information via communication interface 12 4 1 Reading out diagnostic information Diagnostic information can be read out via Modbus RS485 register addresses Via register address 6821 data type string di...

Страница 62: ...rement The measured value output via Modbus RS485 and the totalizers assume the defined alarm condition A diagnostic message is generated Warning The device continues to measure The measured value output via Modbus RS485 and the totalizers are not affected A diagnostic message is generated Logbook entry only The device continues to measure The diagnostic message is entered only in the Event logboo...

Страница 63: ...arm 273 Main electronic failure Change electronic F Alarm 274 Main electronic failure Change electronic S Warning 1 311 Electronic failure 1 Reset device 2 Contact service F Alarm 390 Special event 2 Contact service F Alarm 391 Special event 6 Contact service F Alarm 392 Special event 10 Contact service F Alarm 1 Diagnostic of configuration 410 Data transfer 1 Check connection 2 Retry data transfe...

Страница 64: ...ocess cond 2 Increase system pressure S Warning 1 912 Inhomogeneous S Warning 1 913 Medium unsuitable 1 Check process conditions 2 Check electronic modules or sensor S Alarm 1 944 Monitoring failed Check process conditions for Heartbeat Monitoring S Warning 1 948 Tube damping too high Check process conditions S Warning 990 Special event 4 Contact service F Alarm 991 Special event 8 Contact service...

Страница 65: ...ast device restart Days d hours h minutes m and seconds s Operating time Indicates how long the device has been in operation Days d hours h minutes m and seconds s 12 8 Diagnostic list Up to 5 currently pending diagnostic events can be displayed in the Diagnostic list submenu along with the associated diagnostic information If more than 5 diagnostic events are pending the events with the highest p...

Страница 66: ...s list submenu Navigation path Diagnostics Event logbook Filter options Filter categories All Failure F Function check C Out of specification S Maintenance required M Information I 12 9 3 Overview of information events Unlike a diagnostic event an information event is displayed in the event logbook only and not in the diagnostic list Info number Info name I1000 Device ok I1089 Power on I1090 Confi...

Страница 67: ...ieldbus defaults Every parameter is reset to fieldbus default values To delivery settings Every parameter for which a customer specific default setting was ordered is reset to this customer specific value All other parameters are reset to the factory setting This option is not visible if no customer specific settings have been ordered Restart device The restart resets every parameter whose data ar...

Страница 68: ... the transmitter Max 32 characters such as letters or numbers LPGmass Order code Shows the device order code It can be found in the Order code field on the nameplate Character string composed of letters numbers and certain punctuation marks e g Extended order code 1 Shows the 1st part of the extended order code It can be found in the Ext ord cd field on the nameplate Character string Extended orde...

Страница 69: ...rrent version or the previous version using the service interface For the compatibility of the firmware version with the previous version the installed device description files and operating tools observe the information about the device in the Manufacturer s information document The manufacturer s information is available In the Download Area of the Endress Hauser web site www endress com Downloa...

Страница 70: ...easuring and test equipment Endress Hauser offers a wide variety of measuring and test equipment such as W M or device tests Your Endress Hauser Sales Center can provide detailed information on the services List of some of the measuring and testing equipment 73 13 3 Endress Hauser services Endress Hauser offers a wide variety of services for maintenance such as recalibration maintenance service or...

Страница 71: ...e cycle management database 14 2 Spare parts W M Device Viewer www endress com deviceviewer All the spare parts for the measuring device along with the order code are listed here and can be ordered If available users can also download the associated Installation Instructions Measuring device serial number Is located on the nameplate of the device Can be read out via the Serial number parameter 68 ...

Страница 72: ...vice and Connecting the measuring device sections in reverse order Observe the safety instructions 14 5 2 Disposing of the measuring device LWARNING Danger to personnel and environment from fluids that are hazardous to health Ensure that the measuring device and all cavities are free of fluid residues that are hazardous to health or the environment e g substances that have permeated into crevices ...

Страница 73: ...anagement Improved productivity with information at your fingertips Data relevant to a plant and its components is generated from the first stages of planning and during the asset s complete life cycle W M Life Cycle Management is an open and flexible information platform with online and on site tools Instant access for your staff to current in depth data shortens your plant s engineering time spe...

Страница 74: ...ing system The device consists of a transmitter and a sensor The Safety Barrier Promass 100 is part of the scope of supply and must be implemented to operate the device The device is available as a compact version The transmitter and sensor form a mechanical unit For information on the structure of the device 11 16 3 Input Measured variable Direct measured variables Mass flow Density Temperature C...

Страница 75: ...mode Choose from NaN value instead of current value Last valid value Interface protocol Via digital communication Modbus RS485 Via service interface Plain text display With information on cause and remedial measures Light emitting diodes LED Status information Status indicated by various light emitting diodes The following information is displayed depending on the device version Supply voltage act...

Страница 76: ...essed via Modbus RS485 For Modbus register information see Description of device parameters documentation 16 5 Power supply Terminal assignment 24 Supply voltage The power unit must be tested to ensure it meets safety requirements e g PELV SELV Transmitter Modbus RS485 for use in non hazardous areas and Zone 2 Div 2 DC 20 to 30 V Modbus RS485 for use in intrinsically safe areas Power supply via Sa...

Страница 77: ...re stored Electrical connection 25 Potential equalization 27 Terminals Transmitter Spring terminals for wire cross sections0 5 to 2 5 mm2 20 to 14 AWG Safety Barrier Promass 100 Plug in screw terminals for wire cross sections0 5 to 2 5 mm2 20 to 14 AWG Cable entries Cable gland M20 1 5 with cable 6 to 12 mm 0 24 to 0 47 in Thread for cable entry NPT G M20 Cable specification 22 16 6 Performance ch...

Страница 78: ...m kg h kg h kg h kg h kg h kg h 8 2000 200 100 40 20 4 15 6500 650 325 130 65 13 25 18000 1800 900 360 180 36 40 45000 4500 2250 900 450 90 50 70000 7000 3500 1400 700 140 US units DN 1 1 1 10 1 20 1 50 1 100 1 500 inch lb min lb min lb min lb min lb min lb min 73 50 7 350 3 675 1 470 0 735 0 147 238 9 23 89 11 95 4 778 2 389 0 478 1 661 5 66 15 33 08 13 23 6 615 1 323 1 1654 165 4 82 70 33 08 16 ...

Страница 79: ...ustment and the process temperature the typical measured error of the sensor is 0 0003 of the full scale value C 0 00015 of the full scale value F Influence of medium pressure The table below shows the effect on accuracy of mass flow due to a difference between calibration pressure and process pressure o r of reading DN o r bar o r psi mm in 8 no influence 15 no influence 25 1 no influence 40 1 no...

Страница 80: ...Installation Mounting requirements 18 16 8 Environment Ambient temperature range 19 Temperature tables Observe the interdependencies between the permitted ambient and fluid temperatures when operating the device in hazardous areas For detailed information on the temperature tables see the separate document entitled Safety Instructions XA for the device Storage temperature 40 to 60 C 40 to 140 F Cl...

Страница 81: ...000 kg m3 0 to 312 lb cf Pressure temperature ratings An overview of the pressure temperature ratings for the process connections is provided in the Technical Information document Flow limit Select the nominal diameter by optimizing between the required flow range and permissible pressure loss For an overview of the full scale values for the measuring range see the Measuring range section 74 The m...

Страница 82: ... US units DN in Weight lbs 10 11 1 14 1 23 2 34 Safety Barrier Promass 100 49 g 1 73 ounce Materials Transmitter housing Order code for Housing option A Compact aluminum coated Aluminum AlSi10Mg coated Cable entries cable glands 1 2 3 A0020640 14 Possible cable entries cable glands 1 Cable entry with M20 1 5 internal thread 2 Cable gland M20 1 5 3 Adapter for cable entry with internal thread G or ...

Страница 83: ...539 904L manifold stainless steel 1 4404 316 316L Process connections For all process connections Stainless steel 1 4404 316 316L List of all available process connections 83 Seals Welded process connections without internal seals Safety Barrier Promass 100 Housing Polyamide Process connections Fixed flange connections EN 1092 1 DIN 2501 flange EN 1092 1 DIN 2512N flange ASME B16 5 flange Internal...

Страница 84: ...Communications and Media Authority ACMA Ex approval The devices are certified for use in hazardous areas and the relevant safety instructions are provided in the separate Safety Instructions XA document Reference is made to this document on the nameplate Modbus RS485 certification The measuring device meets all the requirements of the MODBUS TCP conformity test and has the MODBUS TCP Conformance T...

Страница 85: ...n Brief Operating Instructions Measuring device Documentation code LPGmass KA01242 Technical Information Measuring device Documentation code LPGmass TI01169D Description of device parameters Measuring device Documentation code LPGmass GP01093D Supplementary device dependent documentation Safety Instructions Contents Documentation code ATEX IECEx Ex i XA01323 cCSAus IS XA01411 Special documentation...

Страница 86: ...Supplementary documentation 7 Device locking status 54 Device name Sensor 14 Transmitter 13 Device repair 71 Device revision 36 Device type ID 36 DeviceCare 35 Device description file 36 Diagnostic information Communication interface 61 Design description 60 DeviceCare 59 FieldCare 59 Light emitting diodes 58 Overview 62 Remedial measures 62 Diagnostic list 65 DIP switches see Write protection swi...

Страница 87: ...quipment 70 Measuring device Configuration 40 Conversion 71 Design 11 Disposal 72 Mounting the sensor 20 Preparing for electrical connection 25 Preparing for mounting 20 Removing 72 Repairs 71 Measuring instrument approval 84 Measuring principle 74 Measuring range For liquids 74 Measuring range recommended 81 Measuring system 74 Media 8 Medium pressure Influence 79 Medium temperature Influence 79 ...

Страница 88: ...ration 70 reference operating conditions 77 Registered trademarks 7 Repair of a device 71 Repairs 71 Notes 71 Repeatability 79 Replacement Device components 71 Requirements for personnel 8 Response time 79 Return 71 S Safety 8 Safety Barrier Promass 100 25 Seals Medium temperature range 81 Sensor Medium temperature range 81 Mounting 20 Serial number 13 14 Setting the operating language 40 Settings...

Страница 89: ...ables 26 Transporting the measuring device 16 Troubleshooting General 58 U Use of the measuring device Borderline cases 8 Incorrect use 8 see Designated use User interface Current diagnostic event 64 Previous diagnostic event 64 User roles 33 V Version data for the device 36 Vibration resistance 81 Vibrations 20 W W M 70 71 W M Device Viewer 13 71 Weight SI units 82 Transport notes 16 US units 82 ...