Operating menu
Levelflex FMP55 HART
150
Hauser
"Current output 1 to 2" submenu
The
Current output 2
submenu (→ 150) is only available for devices with two
current outputs.
Navigation
Setup → Advanced setup → Curr.output 1 to 2
Assign current output 1 to 2
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Assign curr.
Description
Select process variable for current output.
Selection
• Level linearized
• Distance
• Electronic temperature
• For FMP55: Measured capacitance
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Additionally for Operating mode = "Interface" or "Interface with capacitance":
• Interface linearized
• Interface distance
• Thickness upper layer
• Relative interface amplitude
Factory setting
For interface measurements
• Current output 1: Interface linearized
• Current output 2
: Level linearized
Additional information
Definition of the current range for the process variables
Process variable
4 mA value
20 mA value
Level linearized
0 %
or the associated
linearized value
100 %
or the associated linearized value
Distance
0 (i.e. level is at the reference
point)
0 %)
Electronic temperature
–50 °C (–58 °F)
100 °C (212 °F)
Measured capacitance
0 pF
4
000 pF
Relative echo amplitude
0 mV
2
000 mV
Analog output adv.
diagnostics 1/2
depending on the parametrization of the Advanced Diagnostics
Interface linearized
0 %
or the associated
linearized value
100 %
or the associated linearized value
Interface distance
0 (i.e. interface at the
reference point)
is at 0 %)
9)
only for devices with two current outputs