
Levelflex FMP55 HART
Operating menu
Hauser
151
Process variable
4 mA value
20 mA value
Thickness upper layer
0 %
or the associated
linearized value
100 %
or the associated linearized value
Relative interface amplitude
0 mV
2
000 mV
1)
the 0% level is defined by
Empty calibration
2)
The 100% level is defined by
Full calibration
It may be necessary to adjust the 4mA and 20mA values to the application (especially
in the case of the
Analog output adv. diagnostics 1/2
option ).
This can be done by the following parameters:
• Expert → Output → Curr.output 1 to 2 → Turn down
• Expert → Output → Curr.output 1 to 2 → 4 mA value
• Expert → Output → Curr.output 1 to 2 → 20 mA value
Current span
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Current span
Description
Select current range for process variable and alarm signal.
Selection
• 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• Fixed current
Factory setting
4...20 mA NAMUR
Additional information
Meaning of the options
Option
Current range for process
variable
Lower alarm signal level Upper alarm signal level
4...20 mA
4 to 20.5 mA
< 3.6 mA
> 21.95 mA
4...20 mA NAMUR 3.8 to 20.5 mA
< 3.6 mA
> 21.95 mA
4...20 mA US
3.9 to 20.8 mA
< 3.6 mA
> 21.95 mA
Fixed current
Constant current, defined in the
Fixed current
• In the case of an error, the output current assumes the value defined in the
Failure
mode
• If the meausred value is out of the measuring range, diagnostic message
Current
output
is issued.
In a HART multidrop loop only one device can use the analog current to transmit a
signal. For all other devices one must set:
•
Current span
=
Fixed current
•
=
4 mA
Содержание Levelflex FMP52
Страница 20: ...Storage Transport Levelflex FMP55 HART 20 Endress Hauser 1 2 4 3 A0015471...
Страница 197: ......
Страница 198: ...www addresses endress com 71344071 71344071...