6 Function group "linearisation" (04)
Prosonic M
32
EHauser
6.2
Function "linearisation" (041)
Linearisation defines the ratio of level to container volume or product weight and allows
a measurement in customer units, e.g. metres, hectolitres etc. The measured value in
(000) is then displayed in the selected unit.
This function is used to select the linearisation modes.
Selection:
•
linear
•
horizontal cyl
•
manual
•
semi-automatic
•
table on
•
clear table
linear
The tank is linear e.g. a cylindrical vertical tank. You can measure in customer units by
entering a maximum volume/weight.
You can select the "
customer unit
"
(042)
. Define the volume value corresponding to the
calibration in "
max. scale
"
(046)
. This value corresponds to an output of 100% (= 20 mA
for HART).
Þ