Prosonic M
4 Function group "safety settings" (01)
Hauser
25
4.5
Function "delay time" (014)
Use this function to enter the delay time (Default = 30 s) after which a warning is
generated on echo loss, or after which the instrument switches to alarm state.
4.6
Function "safety distance" (015)
A configurable safety distance is placed before the "
blocking dist.
"
(059)
(Page 43).
This distance warns you that any further level increase would make the measurement
invalid, because the blocking distance would be compromised.
Enter the size of the safety distance here. The default value is: 0.1 m.
Þ
safety distance
(SD)
blocking dist.
(BD)
Þ