Technical data
EngyVolt RV12
30
Maximum measured error
Extended measured error: IEC 688: 1992
Current (A)
0.5 % of nominal current
Voltage (V)
0.5 % of max. nominal voltage (4 % for I2 in 3-phase 3-wire operation)
Calculated neutral current (A)
4 % of nominal current
Frequency (Hz)
0.1 Hz
Power factor (PF = Cos-Phi)
0 to 1
Power factor is only indicated when the measured VA is over 3 % of range
maximum
Active power (W)
±1 % of nominal power
Reactive power (var)
±1 % of nominal power
Apparent power (VA)
±1 % of nominal power
Active energy (kWh)
Class 1 (IEC 62053-21)
Reactive energy (kvarh)
±1 % of measuring range
THD
1 % up to 31st harmonic
Display repetition rate
1 s typically up to >99 % of the full scale value
Measurement and calculation interval
Max. 300 ms (maximum with %THD measurement)
Influence of ambient
temperature
Current and voltage: 0.013 %/°C (0.0072 %/°F) of nominal value
Power: 0.018 %/°C (0.01 %/°F) of measuring range
Error change due to
variation of an influence
quantity in the manner
described in Section 6 of
IEC 688:1992
2 x error allowed for the reference condition applied in the test. Error due to temperature
variation as above.
Error in measurement
when a measurand is
within its measuring range,
but outside its reference
range
2 x error allowed at the end of the reference range adjacent to the section of the
measuring range, where the measurand is currently operating / being tested.
Warm-up period
1 minute
10.5 Installation
Mounting location
EngyVolt RV12
Housing for top hat rail mounting as per DIN 43880
Orientation
Vertical