EngyVolt RV12
Technical data
29
10.2 Output
Output signal
Pulse output
Number
EngyVolt RV12: 1
EngyVolt RV15: max. 2 (optional, via extension modules)
Contact load
50 mA maximum at 250 V AC
Version
Semiconductor relay
RS485 MODBUS
Number
EngyVolt RV12: 1
EngyVolt RV15: 1 (optional, via extension module)
Type
Two-wire, half-duplex
Baud rate
2400, 4800, 9600, 19200, 38400
10.3 Power supply
Supply voltage
AC nominal voltage
110 to 400 V AC ±10 %
DC nominal voltage
120 to 350 V DC ±20 %
Power consumption
5 VA
Electrical connection
The measuring device is designed exclusively for operation on external current
converters.
The multifunction EngyVolt RV12 and RV15 electrical energy meters are suitable for
single-phase and three-phase power systems with 3 or 4 wires.
The "S2" secondary terminals of the current converters are connected in the electrical
energy meter. Only one protective ground connection is provided for this reason.
Terminals
Screw-clamp terminals 0.05 to 2.5 mm² (30 to 14 AWG)
10.4 Performance characteristics
Reference operating
conditions
Reference temperature
23 °C ±1 °C (73.4 °F ±1.8 °F)
Input wave form
50 or 60 Hz ±2 %
Sinusoidal (distortion factor < 0.005)
Supply voltage
Nominal voltage ±1 %
Supply voltage frequency (with
AC)
Nominal frequency ±1 %
Supply voltage wave form
Sinusoidal (distortion factor < 0.05)