EngyVolt RV12
Wiring
13
4.2.3
Connection in 3-phase, 4-wire power network
N
L3
L2
L1
AUX
PULSE MODBUS
CT INPUTS
S1
VOLTAGE INPUTS
L1
L2
L3
N
2
3
4
4
B
A
G -I3+ -I2+ -I1+
1
P1
L1
L2
L3
N
S1
S1
A0016405
5
Connection in 3-phase, 4-wire power network
1
Fast-acting fuse 1 A
2
Slow-blow fuse 1 A
3
Supply voltage
4
Load
The "S2" secondary terminals of the current transformers are connected in the
multifunction electrical energy meter. Only one protective ground connection must be
provided for this reason.
4.3
Connecting the outputs
4.3.1
RS485 interface for communication via Modbus RTU or
Metasys N2
The RS485 Modbus RTU interface is connected to the terminals labeled A, B, G which are
provided for this purpose (→ 3, 11).
A shielded, two-wire cable is recommended for the connection between the RS485 master
and the measuring device. A cable that is specially designed for connecting RS485
interfaces should be used where possible. However, satisfactory results can be achieved
with most shielded cables for connection distances of just a few meters. Cat IV network
cables also deliver satisfactory results. Given that the measuring device communicates with
an external device via an RS485 connection, distances of up to 1200 m can be covered
under good conditions. Electrical interference or other negative conditions can reduce the
distance over which reliable operation is possible.