Residual ripple
4 to 20 mA HART
• Max. ripple (measured at 500
Ω
) 47 to 125 kHz: U
ss
≤
200 mV
• Max. noise (measured at 500
Ω
) 500 Hz to 10 kHz: U
eff
≤
= 2.2 mV
0.1 to 1.2 mA analog
In the range 1 Hz to 100 kHz: max. failsafe value U
SS
≤
1 V
Performance characteristics
Reference operating
conditions
• As per DIN 16086
• Calibration temperature: +25°C (+77°F)
Position during calibration
Zero-point increase
90% of measuring range
Long-term stability
±0.1% of URL
1
per 6 months
Linearity
Linearity as per the limit point method:
– ±0.2% of the set span
1
– Optional: ±0.1% of the set span
1
Hysteresis
±0.1% of URL
1
Influence of ambient
temperature
±0.01%/10 K of URL
1
Influence of medium
temperature
±0.1%/10 K of URL