5 Electrical Installation

ControlCare Panel PC SPC150

10

Hauser

5

Electrical Installation

ControlCare Panel PC SPC150 is an "IT system" in accordance with EN 60950, with supply voltage 
of 24 VDC.

5.1

General precautions

Connections for interference free operation:

•  The EMC approval requires that signal connections are made with shielded cables and metal 

connectors only. 

•  To ensure optimal electrical shielding, all plugged connections are to be screwed or locked into 

position. 

•  Signal cables may not be laid in the same cable trays as power cables.
•  Before commissioning the system, check all cable connections.
•  Ensure that the permissible values for voltages and signals are upheld. 

Safe discharge of electrical disturbances:

•  Connect the Panel PC and cabinet by the shortest possible route to a central earth. 
•  Ensure good electrical connection between Panel PC and cabinet (low-impedance).
•  Use an earth connection conductor of minimum 2.5 mm² (0.1 in

2

) diameter.

Special precautions for 24 VDC devices:

•  The panel PC may be connected to a safety extra low voltage (SELV) circuit only. 
•  The circuit transformer must fulfil the pertinent standards. 

Содержание ControlCare SPC150

Страница 1: ...ControlCare SPC150 BA045S 04 en 03 06 Version 1 00 xx 70103679 Operating Instructions ControlCare SPC150 12 Panel PC as P View Web client...

Страница 2: ......

Страница 3: ...ctrical Installation 10 5 1 General precautions 10 5 2 Power supply 11 5 2 1 24 VDC power supply 11 5 2 2 Plug connector 11 5 2 3 Option ventilator kit 11 5 3 Peripherals 12 5 3 1 Access 12 5 3 2 Keyb...

Страница 4: ...ered trademark of the HART Communication Foundation Houston USA Microsoft Windows Windows 2000 Windows XP and the Microsoft logo are registered trademarks of the Microsoft Corporation Acrobat Reader i...

Страница 5: ...l data must be upheld Explosion hazardous areas The device may not be installed in explosion hazardous areas Repair Do not open the device housing It contains no components that need be maintained or...

Страница 6: ...ifications in the certificate or in a safe area Explosion hazardous area Symbol used in drawings to indicate explosion hazardous areas Devices located in and wiring entering areas with the designation...

Страница 7: ...g to us 2 1 2 Scope of delivery Before installing the device please check that the delivery is complete and undamaged The scope of delivery comprises ControlCare Panel PC SPC150 with preinstalled P Vi...

Страница 8: ...e device type can be derived from the product code by using the table below SPC150 ControlCare Panel PC as P View Web Client Monitor 12 12 Memory extension A B 256 MB 512 MB Compact Flash 1 2 512 MB 1...

Страница 9: ...ver The connection is established by entering the P View server URL in Internet Explorer just as in Internet Depending upon user requirements the P View client is automatically started and the connect...

Страница 10: ...10 F It is important that the device does not overheat during operation Ventilation slits at the top and bottom of the housing allow air to circulate and cool the device during operation Ensure that t...

Страница 11: ...er gasket is properly seated Check that there is enough clearance to remove the panel from the cut out Fig 4 2 shows the dimensions in mm in for the cut out Fig 4 2 Dimensions in mm in for the cut out...

Страница 12: ...into position Signal cables may not be laid in the same cable trays as power cables Before commissioning the system check all cable connections Ensure that the permissible values for voltages and sig...

Страница 13: ...ircuit to EN 60950 5 2 2 Plug connector The 24 VDC socket for the plug connector is to be found on the righthand side of the housing Tab 5 1 Plug connector for 24 VDC To prepare the Panel PC for opera...

Страница 14: ...3 1 Access The ports for peripherals and the external compact flash receptacle are on the bottom of the housing see Fig 5 2 Fig 5 2 Connections for peripheral devices 5 3 2 Keyboard Various keyboard...

Страница 15: ...t flash Controlcare Panel PC SPC150 is equipped with an internal compact flash card on which the system software is stored In order to store user data and programs an external compact flash card is av...

Страница 16: ...B B Tab 5 3 USB double Sub D male connector 9 pin Pin Signal Description Input Output 1 DCD Data Carrier Detect I 2 RxD Receive Data I 3 TxD Transmit Data O 4 DTR Data Terminal Ready O 5 GND Signal Gr...

Страница 17: ...the connection of an external PS 2 keyboard Tab 5 5 PS 2 keyboard HD Sub D female connector 15 pin Pin Signal Pin Signal Pin Signal 1 RED 6 GND 11 N C 2 GREEN 7 GND 12 DDC DAT 3 BLUE 8 GND 13 HSYNC 4...

Страница 18: ...established automatically when the Panel PC is switched on Alternatively the Web client connection is made as in Internet by entering the P View server URL in Internet Explorer 6 2 Operation Operation...

Страница 19: ...ostatic change on your body must be brought to the same level as that of the ControlCare Panel PC SPC150 and its components To this end touch the metal housing Do the same for any tools you are using...

Страница 20: ...sconnect it from the power supply Remove all connection cables Fig 7 2 Opening the housing After the hood has been removed the basic board with its various covered elements are visible Loosen the two...

Страница 21: ...s described in Chapter 7 2 2 3 Using a medium size flat blade screwdriver carefully lift the battery until it can be released from its socket 4 Insert the new battery in the socket such that the mark...

Страница 22: ...s operating temperature symmetry of the lamp supply voltage The times indicated below are typical values taken from the manufacturer s data sheets We recommend that the backlights are replaced after t...

Страница 23: ...ControlCare Panel PC SPC150 Screen size 12 1 diagonal Type Active matrix LCD TFT color Resolution 800 x 600 pixel SVGA Operation Touchscreen Attribute 12 ControlCare Panel PC SPC150 Communication 1x...

Страница 24: ...tion Storage with natural convection 5 C to 45 C vertical 20 C to 60 C Relative humidity max 50 at 40 C non condensing max 90 at 20 C non condensing Surrounding air free from corrosive gases EMC Intef...

Страница 25: ...61 5 10 3 13 5 0 5 0 0 0 4 0 16 0 0 0 31 1 2 82 3 2 84 5 3 3 275 10 8 335 13 2 249 x 187 9 8 x 7 4 Dimensions in mm in 196 7 7 78 5 3 1 0 0 0 12 5 0 45 39 5 1 5 167 5 6 6 295 5 11 7 322 5 12 75 335 13...

Страница 26: ...otection 4 F Fastening 9 Function 7 I Identification 5 Installation 3 10 K Keyboard 12 L Location 8 M Maintenance 17 Monitor 13 Mouse 12 O Operating conditions 22 Operation 3 16 P Power supply 11 PS 2...

Страница 27: ......

Страница 28: ...www endress com worldwide...

Отзывы: