6 Going On-line
ControlCare Field Controller: Commissioning and Configuration
48
Hauser
5 Change the IP address and the Subnet Mask of the computer, so that it is in the same subnet as
the Field Controller.
–
IP Address 192.168.164.XXX and network mask (Subnet Mask) 255.255.255.0.
–
Do not use the addresses 192.168.164.100 or 101,as these are reserved as default addresses
for the Field Controllers SFC162 and SFC173 respectively
6 Click on the
OK
button to complete the procedure
Set the Field Controller IP
address
7 Now call FC Tools:
Programs =>Hauser=>ControlCare=>Tools=>FC Tools
8 Choose the Field Control (OPC) Server path, default
Local,
then press
Connect
9 Select the desired Field Controller module option
Module
using its serial number as reference.
The serial number is printed on the inside of the module door.