ControlCare Field Controller: Commissioning and Configuration
5 Configuring the Field Controller
Hauser
31
Temperature Block
parameters
Parameter
Valid
range/
Options
Default
value
Description/Action
ST_VER
0
Increments on every static parameter change
TAG_DESC
blanks
User specific text of 32-characters to uniquely identify the
block
STRATEGY
0 to 255
0
User specific value that may be used in configuration and
diagnositics as a key in sorting block information
ALERT_KEY
1 to 255
1
User specific value that may be used in sorting the alarms and
events generated by the block
*MODE_BLK
TARGET
O/S
Set to AUTO
BLOCK_ERR
0 to 15
Error status of hardware and software components associated
with the block
REMOTE_IO
Set to Remote I/O master
*CHANNEL.
0
The rack and slot number of the associated SFC 445 module
coded as RRS
TEMP_0...TEMP_7
The temperature value at input point 0...7
VALUE_RANGE_0....
VALUE_RANGE_7
0-100%
When the point is connected to an AI block, this is a copy of
XD_SCALE.
*SENSOR_CONNECTION_0.
..
SENSOR_CONNECTION_7
1, 2, 3
1
Type of sensor connection for points 0...7
1 = differential, 2 = 2-wire, 3 = 3-wire
*SENSOR_TYPE_0
...
SENSOR_TYPE_7
menu
Pt100
The type of sensor connected to points 0...7
(Select from pull-down menu)
UPDATE_EVT
This alert is generated by any change to the static data
BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
*Parameters must be configured for every input used, every SFC445 module requires a separate Temperature Block