Cerabar S 4 to 20mA HART
Description of parameters
Hauser
33
Table 14: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
SIMULATION MODE
Parameter name
Description
SIMULATION MODE (413)
Options
Switch on simulation and select simulation type.
Any simulation running is switched off if the measuring mode or level type is changed.
Options
:
• None
• Pressure,
see also this table, parameter description for SIM. PRESSURE.
• Tank content,
see also this table, parameter description for SIM. TANK CONT.
• Current,
see also this table, parameter description for SIM. CURRENT
• Alarm/warning, ,
see also this table, parameter description for SIM. ERROR NO.
P01-MIDxxxxx-05-xx-xx-EN-003
Factory setting:
None
SIM. PRESSURE (414)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• SIMULATION MODE = Pressure
Factory setting:
Current pressure measured value
SIM. CURRENT (270)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• SIMULATION MODE = Current value
Factory setting:
Current current value
SIM. ERROR NO. (476)
Entry
Enter message number.
See also SIMULATION MODE.
See also these Operating Instructions, Section 6.1 "Messages", "Code" table column.
Prerequisite:
• SIMULATION MODE = Alarm/warning
Factory setting:
613 (simulation active)
Table 15: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
MESSAGES
Parameter name
Description
ALARM STATUS (046)
Display
Displays the current messages present.
See also these Operating Instructions,
Section 6.1 "Messages" and Section "Confirming messages".
Onsite display
• The measured value display shows the message with the highest priority.
• The ALARM STATUS parameter shows all the messages in descending order of
priority. You can scroll through all the messages present with the
O
or
S
key.
Operating program
• The "Status" field and the ALARM STATUS parameter show the message with the
highest priority.
P
I
Simulation value pressure
Simulation value
current
Sensor
Current
output
Pressure
Damping
Position
adjust-
ment
Sensor
trim