Description of parameters
Cerabar S 4 to 20mA HART
32
Hauser
INSERT PIN NO (048)
Entry
For entering a code to lock or unlock operation.
!
Note!
• The
symbol on the onsite display indicates that operation is locked. Parameters
which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST
can still be altered.
• If operation is locked by means of the DIP switch, you can only unlock operation again
by means of the DIP switch. If operation is locked by means of the onsite display or
remote operation e.g. FieldCare, you can unlock operation again either by means of the
onsite display or remote operation.
See also Operating Instructions BA00412P, "Locking/unlocking operation".
Options:
• Lock: enter a number between 0 and 9999 that is
100.
• Unlock: enter the number 100.
Factory setting:
100
HistoROM AVAIL. (831)
Display
Indicates whether the optional HistoROM®/M-DAT memory module is connected to the
electronic insert.
See also Operating Instructions BA00412P, Section "HistoROM
®
/M-DAT (optional)".
Options:
• Yes (HistoROM
®
/M-DAT is attached to the electronic insert)
• No (HistoROM
®
/M-DAT is not attached to the electronic insert)
DOWNLOAD SELECT (014)
Options
Select download function from HistoROM to device. The option selected has no effect on
an upload from the device to the HistoROM.
Prerequisite:
• A HistoROM
®
/M-DAT is attached to the electronic insert
(HistoROM AVAIL. = Yes)
Options:
• Configuration copy: With this option, all parameters apart from the TRANSMITTER
SERIAL No, DEVICE DESIGN., CUST. TAG NUMBER, LONG TAG NUMBER,
ADDITIONAL INFO., BUS ADDRESS and the parameters of the POSITION
ADJUSTMENT and PROCESS CONNECTION group are overwritten.
• Device replacement: With this option, all parameters except for TRANSMITTER
SERIAL No, DEVICE DESIGNATION and the parameters of the POSITION
ADJUSTMENT and PROCESS CONNECTION group are overwritten.
• Electronics replace: With this option, all parameters except for the parameters of the
POSITION ADJUSTMENT group are overwritten.
Factory setting:
Configuration copy (if HistoROM
®
/M-DAT is attached to the electronic insert)
HistoROM CONTROL (832)
Options
For selecting the direction for copying the data.
See also Operating Instructions BA00412P, Section "HistoROM
®
/M-DAT (optional)".
Prerequisite:
• A HistoROM
®
/M-DAT is attached to the electronic insert
(HistoROM AVAIL. = Yes)
Options:
• Abort
• HistoROM
Device
• Device
HistoROM
Factory setting:
Abort (if HistoROM
®
/M-DAT is attached to the electronic insert)
Table 13: (GROUP SELECTION
) OPERATING MENU
OPERATING
Parameter name
Description