background image

30786-7-0415

Page 13

GAs sUppLY

The gas pipeline can be brought in through the right or left side of 

the appliance. Consult the current National Fuel Gas Code, ANSI 

Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

recommended Gas pipe Diameter

pipe Length

schedule 40 pipe 

inside Diameter

tubing, type L

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10ft

0-3m

1/2"

12.7mm

3/8"

9.5mm

1/2"

12.7mm

3/8"

9.5mm

11-40ft

4-12m

1/2"

12.7mm

1/2"

12.7mm

5/8"

15.9mm

1/2"

12.7mm

41-100ft

13-30m

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm

1/2"

12.7mm

101-150ft

31-46m

3/4"

19mm

1/2"

12.7mm

7/8"

22.2mm

3/4"

1.9 mm

note:

 Never use plastic pipe. Check to confirm whether your 

local codes allow copper tubing or galvanized.

note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings.

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flexible 

appliance connector cannot exceed three feet in length.

Figure 9

Gas supply pressure (inches w.c.)

Minimum

Normal

Maximum

Natural Gas

4.5"

7.0"

14.0"

LP (Propane)

10.8"

11.0"

14.0"

Manifold Pressure (inches w.c.)

Normal (HI)

Natural Gas

3.5"

LP (Propane)

10.0"

installing a new Main Gas cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. never pressure test with 

appliance connected; control valve will sustain damage!

nOte: 

The millivolt gas controls are equipped with a captured screw 

type pressure test point, therefore it is not necessary to provide a 

1/8" test point up stream of the control.
When using copper or flex connector use only approved fittings. 
The appliance and it’s individual shut off valve must be disconnected 

from supply piping system during any pressure testing of that system 

at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system 

by closing its individual manual shut off valve during any pressure 

testing of the gas supply piping system at test pressures equal to 

or less than 1/2 psig (3.5kPa).

Attention!

 If one of the procedures results in pressures in excess of 

1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result 

in a hazardous condition.

checking Manifold pressures

Both Propane and Natural gas valves have a built-in pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 4.5" w.c. 

(1.120kPa) for the purpose of input adjustment to a maximum of 

14.0" w.c. (3.484kPa). Propane gas models will have a manifold 

pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 10.8" w.c. 

(2.68kPa) for the purpose of input adjustment to a maximum of 

14.0" w.c. (3.484kPa).  

ELECTRICAL ACCESS

GAS LINE ACCESS

4 1/8”

2 3/8”

5 1/2”

5 7/8”

Figure 10

Содержание DVP36PP32EN-3

Страница 1: ...injury death or property damage Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any a...

Страница 2: ...ar Vent Run 32 Termination Clearances 33 Vent Clearances 34 Vent System Identification 35 Framing and Finishing 36 37 Horizontal Termination 38 DVVK 4RE Vent Kit Installation Instructions 39 41 DVVK 4...

Страница 3: ...DWARE PACKAGE Note Hardware shown to scale where possible 10 X PHILLIPS HEX HEAD SCREW 24 PENINSULA MODELS 16 SEE THROUGH MODELS NAILING FLANGE 8 CORNER TIE CANOPY 2 PENINSULA MODELS ROMEX CONNECTOR 2...

Страница 4: ...e to excessive lint from carpeting bedding materials etc It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Do not put anything around th...

Страница 5: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Страница 6: ...ons shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum...

Страница 7: ...ith the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from theAmerican National Standards Institute Inc 11 West 42nd St New Yor...

Страница 8: ...tension Kit DVEK 25 25 Vent Extension Kit NOTE Air shutter settings are factory minimum settings Some venting configurations may require minor air shutter adjustments for optimum performance SPECIFICA...

Страница 9: ...D D M M N N A A H H J I I 17 21 HORIZONTAL VENT CONNECTION SEE THRU PENINSULA J G MODEL DVP36SP32E DVP36PP32E A 34 3 4 34 3 4 B 39 39 C 24 24 D 22 22 E 36 36 F 29 1 4 32 5 8 G 22 22 H 41 1 8 41 1 8 I...

Страница 10: ...ed to the fireplace This is a heating appliance The flow of heat can ignite combustibles Mantel Chart Figure 3 MANTEL 18 3 8 17 1 8 14 3 8 12 3 8 11 3 8 10 3 8 9 3 8 8 3 8 7 3 8 6 3 8 2 1 4 1 1 2 3 4...

Страница 11: ...he canopy will slide under the flange of the Rear Mantel Corner Bracket Align the holes in the canopy with the corner bracket and loosely install a 10 x 1 2 Hex Head screw to retain 3 Position the Fro...

Страница 12: ...nstall your Direct Vent Fireplace a minimum of 1 3 4 inches clearance must be maintained from the perpendicular wall and the front opening of the appliance However on the vent end of the fireplace if...

Страница 13: ...he action of liquefied petroleum gases The gas lines must be checked for leaks by the installer This should be done with a soap solution watching for bubbles on all exposed connections and if unexpose...

Страница 14: ...e inlet vent collar to the rear of the fireplace with 8 screws 7 This completes the conversion for a rear vent application SPECIAL VENT SYSTEMS The following vent systems are acceptable for use with t...

Страница 15: ...e installation for the fireplace it is necessary to determine where the unit is to be installed and whether optional accessories are desired Gas supply piping should also be planned at this time A gas...

Страница 16: ...raming brackets are shipped as flat brackets that can be attached to the ends of the fireplace prior to sliding fireplace into framed opening Once the fireplace is slid into position the framing brack...

Страница 17: ...the appliance is installed directly on carpeting tile or other combustible material other than wood flooring it shall be installed on a metal or wood panel extending the full width and depth of the ap...

Страница 18: ...PTIONAL Figure 17 Attention Cold climate installation recommendation When installing this unit against a non insulated exterior wall it is recommended that the outer walls be insulated to conform to a...

Страница 19: ...9 1 2 12 11 1 8 to 12 1 2 Figure 20 vertical 90 elbow to horizontal out the wall 90 ELBOW A PIPE LENGTH VENT CAP NOTE 1 FOOT VERTICAL VENT MIN REQUIRED WHEN TOP VENTING WITH HORIZONTAL TERMINATION 9 2...

Страница 20: ...educed by 18 45cm This does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example Accordingtothechartthemaximumhorizontal ventleng...

Страница 21: ...de level a snorkel kit is recommended See page 38 It allows installation depth down to 7 178mm below grade level The 7 178mm is measured from the center of the horizontal vent pipe as it penetrates th...

Страница 22: ...be 11 279 4 mm high x 10 254mm wide with its center line determined by the amount of vertical rise and horizontal run of the termination See Figure 26 When locating the hole it must be noted that the...

Страница 23: ...alified field service per son Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow Inspect entire venting system to ensure proper function Pleas...

Страница 24: ...Vertical Flex Termination Kit WARNING Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches 305mm above the roof WARNING Refer to your fireplac...

Страница 25: ...9 1 2 x 9 1 2 square See Fig ure 29 5 Next determine the location for the cutout in the roof opening This opening must be large enough to provide a minimum 1 air space clearance from the vertical ven...

Страница 26: ...step 5 Feed the flex vent end down through the roof opening and firestop thimble assembly installed in steps 4 through 6 14 Secure the roof support assembly to the roof sheathing with at least 4 nails...

Страница 27: ...ctices 21 An additional storm collar band is provided in kit that may be used as an attic insulation shield The collar can be installed around the flex pipe or hard pipe just above the firestop thimbl...

Страница 28: ...NNECTOR 7 DIA ADAPTER COLLAR WITH GASKET CLAMPS SEE THRU DIRECT VENT FIREPLACE NOTE DVVK 4FV KIT MAXIMUM HEIGHT INCLUDING FIREPLACE IS 13 TO EXTEND VENT RUN AN ADDITIONAL VENT EXTENSION KIT IS NECESSA...

Страница 29: ...er by 6 ft MF07ALA2F006 1 5 4 7 x 48 Rigid Pipe Assembly MF100554 1 6 Firestop Thimble Assembly MF100124 1 7 Roof Flashing 0 12 to 6 12 MF100091 1 8 7 Flex Adapter Collar with Gasket MF100524 1 9 7 St...

Страница 30: ...6 Figure 37 Figure 38 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 Example H2 2ft 2 90 90 6ft V1 21ft H 8ft V 15ft Example H2 3ft H3 1ft 4ft 90 90 90 6ft V1 21ft H 10ft V 21ft Example H1 2ft V1 20ft H 2ft...

Страница 31: ...he indicated dimension and position the unit in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 12 feet 4 inches the horizontal run to the outer wall flange must...

Страница 32: ...30786 7 0415 Page 32 Figure 40 Figure 41 Figure 42 Figure 43 H1 18 MAX H1 18 inches max Model Maximum Pipe Length H1 DVP36 SP PP 18 Model Maximum Pipe Length H1 DVP36 SP PP 18 EXAMPLES REAR VENT RUN...

Страница 33: ...ace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flue...

Страница 34: ...center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other applia...

Страница 35: ...ERMINATION MAXIMUM OF THREE 90 ELBOWS STORM COLLAR ROOF FLASHING WALL THIMBLE HORIZONTAL TWO 90 ELBOWS TERMINATION MAXIMUM OF 90 ELBOW OR 45 ELBOW 90 ELBOW CEILING FIRESTOP WALL STRAP PIPE LENGTH Spec...

Страница 36: ...sition the firestops on both sides of the 10 inch x 11 inch hole previously cut Secure with nails or screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the ve...

Страница 37: ...30786 7 0415 Page 37 Figure 51 FRAMING AND FINISHING continued Figure 49 Figure 50...

Страница 38: ...to install a vinyl siding standoff Thevinylsidingstandoffwillbeinstalledbetweentheventtermination andtheexteriorwall SeeFigure52 Thishorizontalventtermination bolts onto the flat portion of the vinyl...

Страница 39: ...Measure the total wall thickness to determine whether or not the extension thimble is to be used If the combustible wall depth is over 5 3 8 137mm then the extension thimble should be used Figure 54...

Страница 40: ...rews 12 Seal the 4 102mm diameter flue outlet tube Follow instruc tions and diagram Figure 58 13 Fasten 4 102mm diameter flue outlet tube in place Do not twist the flue outlet tube into the fireplace...

Страница 41: ...high temperature sealant to the opposite end of the tube on the inside of the tube The end with the gasket will attach to the back of the unit Continue with Step 13 Connecting to Rigid Vent System If...

Страница 42: ...lex Vent pipe 5 Install the Wall Firestop Thimble assembly as required through the wall Refer to the venting charts in the fireplace manual to determine the proper height and size of the vent opening...

Страница 43: ...es as shown in Figure 60 General Maintenance Conduct an inspection of the venting system semi annually Recommended areas to inspect are as follows 1 Check areas of the venting system which are exposed...

Страница 44: ...ent high wind vertical top Please refer to the instructions included with the Air Inlet Baffle Kit for proper installation Reassembly and Resealing Vent Pipe System Attach vent pipe to inlet and outle...

Страница 45: ...rockwool will break down and new rockwool will need to be placed to recreate the original glowing embers effect Remove all old rockwool from the appliance and apply new rockwool as shown in Figure 63...

Страница 46: ...annoying smoke and smells as they are burned off during the initial operation of the appliance possibly causing headaches or eye or lung irritation This is a normal and temporary occurrence The initi...

Страница 47: ...urging and subsequent lightings never allow the gas valve control knob to remain depressed in the pilot position without pushing the piezo ignitor button at least once every second 2 During the operat...

Страница 48: ...ceiver that is a component in the FREC Turn the REMOTE OFF ON switch to the REMOTE position Follow instructions in the FREC to complete installation NOTE If electric 120 colt fails in FREC and immedia...

Страница 49: ...30786 7 0415 Page 49 Figure 66 OPTIONAL THERMOSTAT OPTIONAL WALL SWITCH STANDING PILOT WIRING DIAGRAM...

Страница 50: ...s To Fireplace FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A Thi...

Страница 51: ...hewireconnectionsfromthethermopileatthegas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP T...

Страница 52: ...to cling to the glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended that the glass be cleaned two or three times with a non abrasive household cl...

Страница 53: ...BRICK LINER BRACKET 23 24710 24710 BURNER ASSEMBLY 24 24144 24144 GRATE ASSEMBLY 25 24282 24282 BURNER SUPPORT 26 24283 24283 BURNER BASE 27 11269 11269 GAS LINE BRACKET 28 24296 24296 TUBING ASSEMBL...

Страница 54: ...0786 7 0415 Page 54 DVP36SP PARTS VIEW 1 2 2 5 6 7 8 9 10 11 12 13 14 15 16 18 18 19 20 21 22 22 23 24 24 25 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 3 3 4 4 17 17 5 5 5 5 5 5 52...

Страница 55: ...7 0415 Page 55 DVP36PP PARTS VIEW 1 2 2 5 5 5 5 6 7 8 9 10 11 12 13 14 15 16 17 17 18 19 20 21 23 24 25 25 26 27 28 29 30 47 48 49 50 51 52 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 45 46 3 3 4 4...

Страница 56: ...remove the tab on the side of the receptacle hot side to split receptacle This will be required to separate blower and Accent Light circuits 2 Power for switched and live sides of Duplex Receptacle mu...

Страница 57: ...now be accessed Note Do not handle the lamp bulb with bare fingers protect with clean dry cloth The lamp will pull straight out of the socket Replace with 25W 120 Volt Halogen bulb When re installing...

Страница 58: ...llation of the wiring be performed by a qualified electrician See Figure 70 1 If installed turn OFF gas supply to fireplace 2 If applicable turn OFF electric supply to fireplace 3 Remove bottom louver...

Страница 59: ...by letters A and B in Figure 75 on page 60 FAN CONTROL SWITCH WIRE ASSEMBLY FROM FAN CONTROL SWITCH Figure 71 7 Route the wires away from moving parts of the blower assem bly and retain wires together...

Страница 60: ...g can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify pr...

Страница 61: ...Decorative Louver Mission Decorative Louver Arch Decorative Louver Leaf Decorative Frame Rectangle with hinges Note Decorative frame required for use with Empire Comfort Systems decorative door Decora...

Страница 62: ...anty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numbe...

Страница 63: ...wner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be...

Страница 64: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: