background image

30786-7-0415

Page 46

Before you begin: Do not handle the logs with your bare hands! 

Always wear gloves to prevent skin irritation. After handling logs, 

wash your hands gently with soap and water.

All Logs

The positioning of the logs is critical to the safe and clean opera-

tion of this heater. Sooting and other problems may result if the 

logs are not properly and firmly positioned in the appliance.

Instructions for placement of the logs in the fireplace are includ-

ed with the logset. Logset approved for use in the DVP36(S,P)P 

fireplaces include model LSU24RR-2, and must be ordered sepa-

rately.

Flames from the pilot (rear right back side of the pan burner) as 

well as the main flame should be visually checked as the log set 

is installed.
In normal operation at full rate after 10 to 15 minutes, the flame 

appearance should be sets of yellow flames. Natural gas burners 

will tend to have blue flames with yellow flame tips.

nOte:

 All flames will be random by design, flame height will go 

up and down.
Glowing embers (rockwool) can cover the pan burner in areas 

as shown in Figure 63, but very little is necessary to cover these 

areas. Excess ember material causes the yellow flame to become 

orange and stringy. Apply just enough to obtain slow glow and a 

gold or yellow flame.
During manufacturing, fabricating and shipping, various components 

of this appliance are treated with certain oils, films or bonding agents. 

These chemicals are not harmful, but may produce annoying smoke 

and smells as they are burned off during the initial operation of the 

appliance, possibly causing headaches or eye or lung irritation. This 

is a normal and temporary occurrence.

The initial break-in operation should be 5 to 10 minutes on (at the 

highest setting) then let cool for 10 to 15 minutes. Repeat this On/

Off cycle two to three times to cure sealants. Provide additional  

ventilation by opening windows or doors to allow odors to dissipate. 

Any odors remaining after this initial break-in will be slight and will 

disappear with continued use.

periODic cLeAninG – refer to parts diagram for location of 

items discussed below.

• 

Do not use cleaning fluid to clean logs or any part of heater.

• 

Logs  -  brush  with  soft  bristle  brush  or  vacuum  with  brush 

attachment.

• 

Remove  loose  particles  and  dust  from  the  burner  areas, 

controls, piezo covers and grate. Don’t remove ceramic media 

from inside burner box.

• 

Inspect and clean burner air intake hole. Remove lint or particles 

with brush. Failure to keep air intake hole clean will result in 

sooting and poor combustion.

AnnUAL cLeAninG/inspectiOn – refer to parts diagram for 

location of items discussed below.

• 

Inspect and clean burner air intake hole. Remove lint or particles 

with vacuum or brush. Failure to keep air intake hole clean will 

result in sooting and poor combustion.

• 

Inspect and clean all burner ports.

• 

Inspect pilot for proper operation.

• 

Verify flame pattern and log placement for proper operation.

• 

Verify smooth and responsive ignition of main burner.

• 

Check level of ceramic media in burner. Burner should be full, 

up to the level of openings in burner top.

OperAtiOn instrUctiOns/FLAMe AppeArAnce

Содержание DVP36PP32EN-3

Страница 1: ...injury death or property damage Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any a...

Страница 2: ...ar Vent Run 32 Termination Clearances 33 Vent Clearances 34 Vent System Identification 35 Framing and Finishing 36 37 Horizontal Termination 38 DVVK 4RE Vent Kit Installation Instructions 39 41 DVVK 4...

Страница 3: ...DWARE PACKAGE Note Hardware shown to scale where possible 10 X PHILLIPS HEX HEAD SCREW 24 PENINSULA MODELS 16 SEE THROUGH MODELS NAILING FLANGE 8 CORNER TIE CANOPY 2 PENINSULA MODELS ROMEX CONNECTOR 2...

Страница 4: ...e to excessive lint from carpeting bedding materials etc It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Do not put anything around th...

Страница 5: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Страница 6: ...ons shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum...

Страница 7: ...ith the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from theAmerican National Standards Institute Inc 11 West 42nd St New Yor...

Страница 8: ...tension Kit DVEK 25 25 Vent Extension Kit NOTE Air shutter settings are factory minimum settings Some venting configurations may require minor air shutter adjustments for optimum performance SPECIFICA...

Страница 9: ...D D M M N N A A H H J I I 17 21 HORIZONTAL VENT CONNECTION SEE THRU PENINSULA J G MODEL DVP36SP32E DVP36PP32E A 34 3 4 34 3 4 B 39 39 C 24 24 D 22 22 E 36 36 F 29 1 4 32 5 8 G 22 22 H 41 1 8 41 1 8 I...

Страница 10: ...ed to the fireplace This is a heating appliance The flow of heat can ignite combustibles Mantel Chart Figure 3 MANTEL 18 3 8 17 1 8 14 3 8 12 3 8 11 3 8 10 3 8 9 3 8 8 3 8 7 3 8 6 3 8 2 1 4 1 1 2 3 4...

Страница 11: ...he canopy will slide under the flange of the Rear Mantel Corner Bracket Align the holes in the canopy with the corner bracket and loosely install a 10 x 1 2 Hex Head screw to retain 3 Position the Fro...

Страница 12: ...nstall your Direct Vent Fireplace a minimum of 1 3 4 inches clearance must be maintained from the perpendicular wall and the front opening of the appliance However on the vent end of the fireplace if...

Страница 13: ...he action of liquefied petroleum gases The gas lines must be checked for leaks by the installer This should be done with a soap solution watching for bubbles on all exposed connections and if unexpose...

Страница 14: ...e inlet vent collar to the rear of the fireplace with 8 screws 7 This completes the conversion for a rear vent application SPECIAL VENT SYSTEMS The following vent systems are acceptable for use with t...

Страница 15: ...e installation for the fireplace it is necessary to determine where the unit is to be installed and whether optional accessories are desired Gas supply piping should also be planned at this time A gas...

Страница 16: ...raming brackets are shipped as flat brackets that can be attached to the ends of the fireplace prior to sliding fireplace into framed opening Once the fireplace is slid into position the framing brack...

Страница 17: ...the appliance is installed directly on carpeting tile or other combustible material other than wood flooring it shall be installed on a metal or wood panel extending the full width and depth of the ap...

Страница 18: ...PTIONAL Figure 17 Attention Cold climate installation recommendation When installing this unit against a non insulated exterior wall it is recommended that the outer walls be insulated to conform to a...

Страница 19: ...9 1 2 12 11 1 8 to 12 1 2 Figure 20 vertical 90 elbow to horizontal out the wall 90 ELBOW A PIPE LENGTH VENT CAP NOTE 1 FOOT VERTICAL VENT MIN REQUIRED WHEN TOP VENTING WITH HORIZONTAL TERMINATION 9 2...

Страница 20: ...educed by 18 45cm This does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example Accordingtothechartthemaximumhorizontal ventleng...

Страница 21: ...de level a snorkel kit is recommended See page 38 It allows installation depth down to 7 178mm below grade level The 7 178mm is measured from the center of the horizontal vent pipe as it penetrates th...

Страница 22: ...be 11 279 4 mm high x 10 254mm wide with its center line determined by the amount of vertical rise and horizontal run of the termination See Figure 26 When locating the hole it must be noted that the...

Страница 23: ...alified field service per son Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow Inspect entire venting system to ensure proper function Pleas...

Страница 24: ...Vertical Flex Termination Kit WARNING Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches 305mm above the roof WARNING Refer to your fireplac...

Страница 25: ...9 1 2 x 9 1 2 square See Fig ure 29 5 Next determine the location for the cutout in the roof opening This opening must be large enough to provide a minimum 1 air space clearance from the vertical ven...

Страница 26: ...step 5 Feed the flex vent end down through the roof opening and firestop thimble assembly installed in steps 4 through 6 14 Secure the roof support assembly to the roof sheathing with at least 4 nails...

Страница 27: ...ctices 21 An additional storm collar band is provided in kit that may be used as an attic insulation shield The collar can be installed around the flex pipe or hard pipe just above the firestop thimbl...

Страница 28: ...NNECTOR 7 DIA ADAPTER COLLAR WITH GASKET CLAMPS SEE THRU DIRECT VENT FIREPLACE NOTE DVVK 4FV KIT MAXIMUM HEIGHT INCLUDING FIREPLACE IS 13 TO EXTEND VENT RUN AN ADDITIONAL VENT EXTENSION KIT IS NECESSA...

Страница 29: ...er by 6 ft MF07ALA2F006 1 5 4 7 x 48 Rigid Pipe Assembly MF100554 1 6 Firestop Thimble Assembly MF100124 1 7 Roof Flashing 0 12 to 6 12 MF100091 1 8 7 Flex Adapter Collar with Gasket MF100524 1 9 7 St...

Страница 30: ...6 Figure 37 Figure 38 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 Example H2 2ft 2 90 90 6ft V1 21ft H 8ft V 15ft Example H2 3ft H3 1ft 4ft 90 90 90 6ft V1 21ft H 10ft V 21ft Example H1 2ft V1 20ft H 2ft...

Страница 31: ...he indicated dimension and position the unit in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 12 feet 4 inches the horizontal run to the outer wall flange must...

Страница 32: ...30786 7 0415 Page 32 Figure 40 Figure 41 Figure 42 Figure 43 H1 18 MAX H1 18 inches max Model Maximum Pipe Length H1 DVP36 SP PP 18 Model Maximum Pipe Length H1 DVP36 SP PP 18 EXAMPLES REAR VENT RUN...

Страница 33: ...ace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flue...

Страница 34: ...center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other applia...

Страница 35: ...ERMINATION MAXIMUM OF THREE 90 ELBOWS STORM COLLAR ROOF FLASHING WALL THIMBLE HORIZONTAL TWO 90 ELBOWS TERMINATION MAXIMUM OF 90 ELBOW OR 45 ELBOW 90 ELBOW CEILING FIRESTOP WALL STRAP PIPE LENGTH Spec...

Страница 36: ...sition the firestops on both sides of the 10 inch x 11 inch hole previously cut Secure with nails or screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the ve...

Страница 37: ...30786 7 0415 Page 37 Figure 51 FRAMING AND FINISHING continued Figure 49 Figure 50...

Страница 38: ...to install a vinyl siding standoff Thevinylsidingstandoffwillbeinstalledbetweentheventtermination andtheexteriorwall SeeFigure52 Thishorizontalventtermination bolts onto the flat portion of the vinyl...

Страница 39: ...Measure the total wall thickness to determine whether or not the extension thimble is to be used If the combustible wall depth is over 5 3 8 137mm then the extension thimble should be used Figure 54...

Страница 40: ...rews 12 Seal the 4 102mm diameter flue outlet tube Follow instruc tions and diagram Figure 58 13 Fasten 4 102mm diameter flue outlet tube in place Do not twist the flue outlet tube into the fireplace...

Страница 41: ...high temperature sealant to the opposite end of the tube on the inside of the tube The end with the gasket will attach to the back of the unit Continue with Step 13 Connecting to Rigid Vent System If...

Страница 42: ...lex Vent pipe 5 Install the Wall Firestop Thimble assembly as required through the wall Refer to the venting charts in the fireplace manual to determine the proper height and size of the vent opening...

Страница 43: ...es as shown in Figure 60 General Maintenance Conduct an inspection of the venting system semi annually Recommended areas to inspect are as follows 1 Check areas of the venting system which are exposed...

Страница 44: ...ent high wind vertical top Please refer to the instructions included with the Air Inlet Baffle Kit for proper installation Reassembly and Resealing Vent Pipe System Attach vent pipe to inlet and outle...

Страница 45: ...rockwool will break down and new rockwool will need to be placed to recreate the original glowing embers effect Remove all old rockwool from the appliance and apply new rockwool as shown in Figure 63...

Страница 46: ...annoying smoke and smells as they are burned off during the initial operation of the appliance possibly causing headaches or eye or lung irritation This is a normal and temporary occurrence The initi...

Страница 47: ...urging and subsequent lightings never allow the gas valve control knob to remain depressed in the pilot position without pushing the piezo ignitor button at least once every second 2 During the operat...

Страница 48: ...ceiver that is a component in the FREC Turn the REMOTE OFF ON switch to the REMOTE position Follow instructions in the FREC to complete installation NOTE If electric 120 colt fails in FREC and immedia...

Страница 49: ...30786 7 0415 Page 49 Figure 66 OPTIONAL THERMOSTAT OPTIONAL WALL SWITCH STANDING PILOT WIRING DIAGRAM...

Страница 50: ...s To Fireplace FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A Thi...

Страница 51: ...hewireconnectionsfromthethermopileatthegas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP T...

Страница 52: ...to cling to the glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended that the glass be cleaned two or three times with a non abrasive household cl...

Страница 53: ...BRICK LINER BRACKET 23 24710 24710 BURNER ASSEMBLY 24 24144 24144 GRATE ASSEMBLY 25 24282 24282 BURNER SUPPORT 26 24283 24283 BURNER BASE 27 11269 11269 GAS LINE BRACKET 28 24296 24296 TUBING ASSEMBL...

Страница 54: ...0786 7 0415 Page 54 DVP36SP PARTS VIEW 1 2 2 5 6 7 8 9 10 11 12 13 14 15 16 18 18 19 20 21 22 22 23 24 24 25 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 3 3 4 4 17 17 5 5 5 5 5 5 52...

Страница 55: ...7 0415 Page 55 DVP36PP PARTS VIEW 1 2 2 5 5 5 5 6 7 8 9 10 11 12 13 14 15 16 17 17 18 19 20 21 23 24 25 25 26 27 28 29 30 47 48 49 50 51 52 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 45 46 3 3 4 4...

Страница 56: ...remove the tab on the side of the receptacle hot side to split receptacle This will be required to separate blower and Accent Light circuits 2 Power for switched and live sides of Duplex Receptacle mu...

Страница 57: ...now be accessed Note Do not handle the lamp bulb with bare fingers protect with clean dry cloth The lamp will pull straight out of the socket Replace with 25W 120 Volt Halogen bulb When re installing...

Страница 58: ...llation of the wiring be performed by a qualified electrician See Figure 70 1 If installed turn OFF gas supply to fireplace 2 If applicable turn OFF electric supply to fireplace 3 Remove bottom louver...

Страница 59: ...by letters A and B in Figure 75 on page 60 FAN CONTROL SWITCH WIRE ASSEMBLY FROM FAN CONTROL SWITCH Figure 71 7 Route the wires away from moving parts of the blower assem bly and retain wires together...

Страница 60: ...g can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify pr...

Страница 61: ...Decorative Louver Mission Decorative Louver Arch Decorative Louver Leaf Decorative Frame Rectangle with hinges Note Decorative frame required for use with Empire Comfort Systems decorative door Decora...

Страница 62: ...anty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numbe...

Страница 63: ...wner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the ap pliance A bill of sale cancelled check or payment record should be...

Страница 64: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: