Empire Heating Systems DV-210-SG Скачать руководство пользователя страница 13

12433-10-0109

Page 13

1.   Lit match goes out as it enters lighter port. 

 

a.   Certain wind conditions will blow  out match.  Ignite 

match,  and as it flares,  thrust match through opening.

 

b.   Open nearby door or window and relight pilot.

2.   Pilot flames but goes out when knob is released.

 

 

a.   See Lighting Instructions.  Relight Pilot.

 

b.   Relight the pilot and hold knob down longer and harder.  

Close lighter hole cover just after igniting.  Check for a 

good pilot flame.

 

c.   Defective thermopile or defective magnet in safety section 

of valve.  Replace.

3.   Yellow pilot flame. 

 

a.   Obstruction at pilot orifice.

 

b.   Clean and properly size orifice.

4.  Pilot and main burner go out during normal operation.

 

a.   Check millivolts.

 

b.   Check for proper size of pilot flame.

 

c.  Check for defective or weak thermopile.

 

d.  Check input, reduce as needed.

 

e.   Cover on pilot lighter hole must be air tight.

 

f.   Check for tight fit of air and flue tubes at both ends of vent 

assembly.  No obstruction around vent that would prevent 

the wind from hitting all of the vent equally.

5.   Thermostat does not turn the main burner on. 

 

 

a.   Check wiring.

 

b.   Check all millivolt readings.

 

c.   Check for spider in main burner orifice.

6.   Yellow main burner flame soot on the vent cap. 

 

 

a.   Remove main burner to check for obstructions in throat, 

ports and orifices.

 

b.   Install new main burner orifice and pilot orifice.  Refer to 

Parts List on Page 14.

trouBlesHootinG

Содержание DV-210-SG

Страница 1: ...th or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vicin...

Страница 2: ...ifications 6 Gas Supply 7 Clearances 8 Installation Instructions 8 9 Thermostat Location 10 Lighting Instructions 11 Pilot Flame Characteristics 12 Main Burner Flame Characteristics 12 Maintenance 12...

Страница 3: ...ied service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is impera tive that control compartments burners and circulating air passageways...

Страница 4: ...g vehicle trailer or area Finally let the service man and firefighters check for escaped gas Have them air out the area before you return Properly trained LP Gas service people should repair the leak...

Страница 5: ...uiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the exter...

Страница 6: ...erformed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the in...

Страница 7: ...that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign partic...

Страница 8: ...nimum wall depth is 4 1 2 114mm and maximum wall depth is 13 330mm The use of tubes not supplied by the manufacturer result in unsatisfactory performance The furnace is to be located on an outside wal...

Страница 9: ...l Remove 5 127mm diameter air inlet tube from collar of air drop assembly 2 Attach3 76mm diameterflueoutlettubeontoflueoutletcollar oncombustionchamber Besure3 76mm diameterflueoutlet tube is placed a...

Страница 10: ...d be Across the thermopile terminals 400 450 millivolts with ther mostat off Across the thermopile terminals 150 250 millivolts with ther mostat on Across the thermostat wires at the valve less than 3...

Страница 11: ...to desired setting 16 CAUTION Pilot access cover must be kept tightly closed during operation To Turn Off Gas To Appliance FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these inst...

Страница 12: ...ted After this the valve and orifice elbow can be removed as a unit Cleaning The Pilot Burner Cleaning of the pilot may be an annual necessity due to spiders After removing the supply tubing and orifi...

Страница 13: ...properly size orifice 4 Pilot and main burner go out during normal operation a Check millivolts b Check for proper size of pilot flame c Check for defective or weak thermopile d Check input reduce as...

Страница 14: ...HOLE 11 852098 NUT FOR ORIFICE FITTING 12 742134 BURNER ORIFICE DV 210 NAT 12 742133 BURNER ORIFICE DV 215 NAT 12 742297 BURNER ORIFICE DV 210 LPG 12 742282 BURNER ORIFICE DV 215 LPG 13 742038 ORIFICE...

Страница 15: ...12433 10 0109 Page 15 PARTS VIEW...

Страница 16: ...appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong re ceptacle Do not cut or remove th...

Страница 17: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: