To Use the Vent Graph
1. Determine the height of the center of the horizontal vent pipe.
Using this dimension on the Sidewall Vent Graph, locate the
point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 12 feet, 4 inches
the horizontal run to the outer wall flange must not exceed 12 feet,
3 inches.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6 feet, 9 inches,
the horizontal run to the outer wall flange must not exceed 6 feet,
6 inches.
SPECIAL NOTE:
For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be reduced
by 18" (457 mm). This does not apply if the 45-degree elbows
are installed on the vertical part of the vent system. Reduce 3'
for every 90° elbow.
Example:
According to the chart the maximum horizontal vent length
is 20' and if two 45 degree elbows are required in the horizontal
vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per side
wall installation is two. These elbows can be installed in either the
vertical or horizontal run.
Acceptable vertical and horizontal vent run.
Unacceptable vertical and horizontal vent run.
NOTICE:
When rear venting unit, adjust air shutter from 1/16"
open up to between 1/8" and 3/16" for Natural Gas.
Adjust air shutter from 1/4" open to between 5/16" and to 3/8"
for Propane Gas.
NOTE:
When rear venting unit, adjust air shutter from 1/16" open
up to between 1/8" and 3/16" for Natural Gas.
Adjust air shutter from 1/4" open to between 5/16" and 3/8" for
Propane Gas.
Figure 32
Venting Graph (Dimensions in Feet)
VENTING FIREPLACE - REAR
Содержание MILLIVOLT DVD32FP30N-3
Страница 21: ...Page 21 43115 2 0821 Figure 31 EXAMPLES TOP VENT RUN Figure 30 Figure 29...
Страница 41: ...Page 41 43115 2 0821 MILLIVOLT STANDING PILOT WIRING DIAGRAM FP3 SERIES Figure 61...
Страница 47: ...Page 47 43115 2 0821 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING FP7 SERIES...
Страница 48: ...43115 2 0821 Page 48 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING FP7 SERIES...
Страница 65: ...Page 65 43115 2 0821 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...