35919-4-1015
Page 29
Termination clearance for buildings with combustible and noncombustible exteriors.
Vertical Sidewall Installations
Important!
Minimum clearance between vent pipes and combustible
materials is 3 inch(75 mm) on top, and 2 inch (50 mm) on bottom
and sides.
Important!
When vent termination exits through foundation less than
20 inch(508 mm) below siding outcrop, the vent pipe must extend
outward so that the horizontal vent termination is located flush to,
or beyond the outcrop siding.
Information on Various Venting Routes and Components
Important:
It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its balance
between the combustion air intake and the flue gas exhaust, certain
limitations as to vent configurations apply and must be strictly
adhered to.
Figure 57
TERMINATION CLEARANCES
The graph showing the relationship between vertical and horizontal
side wall venting will help to determine the various vent lengths
allowable.
The horizontal vent run refers to the total length of vent pipe from
the flue collar of the fireplace to the face of the outer wall.
The maximum horizontal vent run is 20 feet (6.10 m) when the
vertical vent rise is 8 feet (2.44 m).
See Page 21, Figure 38.
Venting termination shall not be recessed into wall or siding.