42
Getting Started
CG Drives & Automation, 01-6142-01r0
5.3.3 Set reservoir geometry
The reservoir geometry settings are crucial for the auto tune
program and flow estimations. Please enter values as pre-
cisely as possible, failing to do so will result in inaccurate
measurements.
Navigate to menu “[3A31] Level 1” or press toggle button.
Start from the bottom level (level 1) and set a corresponding
area for each change of shape in the reservoir. It is possible to
use 5 levels and areas. Use as many as required, unused lev-
els/areas should be set to 0/Off.
Level 1 [3A31]
Area 1 [3A32]
Level 2 [3A33]
Area 2 [3A34]
Level 3 [3A35]
Area 3 [3A36]
Level 4 [3A37]
Area 4 [3A38]
Level 5 [3A39]
Area 5 [3A3A]
Fig. 50 Sump areas and levels, examples.
Example with round reservoir:
Level= X m,
Area = π
r
2
Level 1 = 0 m
Area 1 = Radius is 0.6 m, area 1 is calculated:
π 0.6
2
= 1.13
m
2
Level 2 = 0.6 m,
Area 2 = Radius is 0.6 m, area 2 is calculated:
π 0.6
2
= 1.13
m
2
Level 3 = 0.5 m
Area 3 = Radius 0.9 m, area 3 is calculated:
π 0.9
2
= 2.54
m
2
Level 4 = 1.5 m
Area 4 = Radius 0.9 m, area 4 is calculated:
π 0.9
2
= 2.54
m
2
Example with rectangular reservoir:
Level= X m,
Area = A x B m
2
Level 1: 0 m
Area 1 : A= 1.2 m, B= 0.5m, area 1 is calculated:
1.2 x 0.5 = 0.6 m
2
Level 2 = 0.6 m,
Area 2 : A= 1.2 m, B= 0.5m, area 2 is calculated:
1.2 x 0.5 = 0.6 m
2
Level 3 = 0.5 m
Area 3 : A= 1.8 m, B= 0.5m, area 3 is calculated:
1.8 x 0.5 = 0.9 m
2
Level 4 = 1.5 m
Area 4 : A= 1.8 m, B= 0.5m, area 4 is calculated:
1.8 x 0.5 = 0.9 m
2
P1
P2
[3A31]Level 1 / [3A32]Area 1
[3A33]Level 2 / [3A34]Area 2
[3A35]Level 3 / [3A36]Area 3
[3A23]Start Level
[3A24]Stop Level
[3A21]Overflow Level
Area calculation:
r
A
B
[3A37]Level 4 / [3A38]Area 4
r = diameter/2