CG Drives & Automation 01-6142-01r0
Technical Data
59
8.7
Fuses and glands
8.7.1 According to IEC ratings
Use mains fuses of the type gL/gG conforming to IEC 269
or breakers with similar characteristics. Check the
equipment first before installing the glands.
Max. Fuse = maximum fuse value that still protects the AC
drive and upholds warranty.
NOTE: The dimensions of fuse and cable cross-section
are dependent on the application and must be
determined in accordance with local regulations.
NOTE: The dimensions of the power terminals used in the
cabinet drive models 300 to 3K0 can differ depending
on customer specification.
Table 32
Fuses, cable cross-sections and glands
Model
Nominal input
current
[A]
Maximum value
fuse
[A]
Cable glands (clamping range ) *
mains / motor
Brake
##-003
2.2
4
M32 opening
M20 + reducer
(6–12 mm(0.24 - 0.47 in))
M25 opening
M20 + reducer
(6–12 mm(0.24 - 0.47 in))
##-004
3.5
4
##-006
5.2
6
##-008
6.9
10
M32 (12–20)/M32 opening
M25+reducer
(10-14 mm(0.39 - 0.55 in))
M25
(10-14 mm(0.39 - 0.55 in))
##-010
8.7
10
##-013
11.3
16
M32 (16–25)/M32 (13–18)
##-018
15.6
20
##-025
22
25
- (12 - 16 mm(0.55 - 0.63 in))
##-026
22
25
M32
(15–21 mm(0.59 - 0.83 in))
M25
##-030
26
35
- (16 - 20 mm (0.63 - 0.79 in))
##-031
26
35
M32
(15–21 mm(0.59 - 0.83 in))
M25
##-036
31
35
- (20 - 24 mm(0.79 - 0.94))
##-037
31
35
M40
(19–28 mm (0.75 - 1.1 in))
M32
##-045
38
50
- (24 - 28 mm(0.94 - 1.1 in))
##-046
38
50
M40
(19–28 mm (0.75 - 1.1 in))
M32
##-058
50
63
- (24 - 28 mm(0.94 - 1.1 in))
##-061
52
63
M50
(27 - 35 mm(1.06 - 1.38 in))
M40
(19–28 mm (0.75 - 1.1 in))
##-072
64
80
- (28 - 32 mm(1.1 - 1.26 in))
##-074
65
80
M50
(27 - 35 mm(1.06 - 1.38 in))
M40
(19–28 mm(0.75 - 1.1 in))
##-088
78
100
- (32 - 36 mm(1.26 - 1.42 in))
##-090
78
100
48: (Ø17-42 mm (0.67 - 1.65 in))
cable flexible leadthrough or M50
opening.
69: (Ø23-55 mm (0.9 - 2.16 in))
Cable flexible leadthrough or M63
opening.
48: (Ø11-32 mm(0.43 - 1.26 in))
Cable flexible leadthrough or M40
opening.
69: (Ø17-42 mm (0.67 - 1.65 in))
Cable flexible leadthrough or M50
opening.
##-105
91
100
- (32 - 36 mm(1.26 - 1.42 in))
##-109
94
100
48: (Ø17-42 mm (0.67 - 1.65 in))
cable flexible leadthrough or M50
opening.
69: (Ø23-55 mm (0.9 - 2.16 in))
Cable flexible leadthrough or M63
opening.
48: (Ø11-32 mm(0.43 - 1.26 in))
Cable flexible leadthrough or M40
opening.
69: (Ø17-42 mm (0.67 - 1.65 in))
Cable flexible leadthrough or M50
opening.
##-142
126
160
- (40 - 44 mm (1.57 - 1.73 in))
- (36 - 40 mm(1.42 - 1.57 in))