32

Functional Description

Emotron AB 01-5016-01r0

7.5.3

Stored values [730]

The shown values are the actual values built up over time. 
Values are stored at power down and updated again at power 
up.

Run Time [731]

Displays the total time that the VSD has been in Run Mode. 

Mains time [732]

Displays the total time that the VSD has been connected to 
the mains supply. This timer cannot be reset.

Energy [733]

Displays the total energy consumption.

7.6

View Trip Log [800]

Main menu with parameters for viewing all the logged trip 
data. In total the VSD saves the last 9trips in the trip mem-
ory. The trip memory refreshes on the FIFO principle (First 
In, First Out). Every trip in the memory is logged on the 
time of the Run Time [731] counter. At every trip, the 
actual values of several parameters are stored and available 
for troubleshooting.

7.6.1

Trip Message log [810]

Display the cause of the trip and what time it occurred. 
When a trip occurs the status menus are copied to the trip 

message log. There are nine trip message logs [810]–[890]
When the tenth trip occurs the oldest trip will disappear..

Trip message [811]-[81N]

The information from the status menus are copied to the 
trip message log when a trip occurs. 

Unit:

h: m: s (hours: minutes: seconds)

Range:

0h: 0m: 0s–65535h: 59m: 59s

Unit:

h: m: s (hours: minutes: seconds)

Range:

0h: 0m: 0s–65535h: 59m: 59s

NOTE: At 65535 h: 59 m the counter stops. It will not 
revert to 0h: 0m.

Unit:

kWh

Range:

0.0–999999kWh

731 Run Time

Stp

h:m:s

732 Mains Time

Stp

h:m:s

733 Energy

Stp

kWh

Unit:

h: m (hours: minutes)

Range:

0h: 0m–65355h: 59m

Trip menu

Copied from

Description

811

711

Process Value

812

712

Motor speed

813

712

Torque

814

714

Shaft Power

815

715

Electrical Power

816

716

Current

817

717

Output voltage

818

718

Frequency

819

719

DC Link voltage

81A

71A

Heat sink temperature

81C

721

VSD Status

81D

723

Digital input status

81E

724

Digital output status

81F

725

Analogue input status 1-2

81G

726

Analogue input status 3-4

81H

727

Analogue output status 1-2

81L

731

Run Time

81M

732

Mains Time

81N

733

Energy

81O

310

View reference

8x0 Trip message

Stp 

h:mm:ss

810 Ext Trip

Stp 

132:12:14

Содержание EMX-D

Страница 1: ......

Страница 2: ...Emotron EMX D Drive system for rotary heat exchanger Instruction manual English...

Страница 3: ......

Страница 4: ...re three plugs Before starting up remove the plug in highest position check the oil level and add oil if necessary Use lubricant according to the type plate Quantity of lubricant in the gearbox is 0 2...

Страница 5: ...oc Rem Key This key is a quick access to menu Language 211 Press this key if you would like to change the language in menu system and Control panel display Language 211 Select the language used in men...

Страница 6: ...01 5016 01 Edition r0 Date of release 2010 09 01 Copyright Emotron AB 2010 Emotron retains the right to change specifications and illustrations in the text without prior notification The contents of...

Страница 7: ......

Страница 8: ...his manual follow the EMC Directive Voltage tests Megger Do not carry out voltage tests Megger on the motor before all the motor cables have been disconnected from the drive system Condensation If the...

Страница 9: ...Emotron AB 01 5016 01r0...

Страница 10: ...sing 10 k potentiometer 17 4 4 7 Switching off 17 5 Getting Started 19 5 1 Connect the mains and motor cables 19 5 2 Remote control 19 5 2 1 Connect control cables and set direction of rotation 19 5 2...

Страница 11: ...4 Emotron AB 01 5016 01r0...

Страница 12: ...urer s certificate contact your supplier for more information or visit www emotron com 1 3 1 Recommendations with respect to EMC In order to fulfil the European EMC Directive 2004 108 EC regarding ele...

Страница 13: ...natural resources For more detailed information about recycling this product please contact the local distributor of the product or visit our home page www emotron com Table 1 Standards Market Standa...

Страница 14: ...efficiency of the heat exchanger rather than having the speed of rotation proportional to the control sig nal This provides good conditions for stable temperature control Fig 2 Relation between contro...

Страница 15: ...itor is connected 2 3 4 Alarm relay A built in relay triggers an alarm at mains supply overvoltage mains supply undervoltage motor overload loss of signal from rotor magnet to rotation monitor e g in...

Страница 16: ...for the rotation monitor is mounted tight on the periphery of the heat exchanger If the housing around the rotor is magnetic itself then the sensor magnet must be isolated from the housing The rotati...

Страница 17: ...d between the motor unit and the control system Motor cable 4 core 1 5 mm2 screened PTC cable 2 core screened min 0 75 mm2 If cables are lengthened ensure that the screening is spliced carefully An ex...

Страница 18: ...e control cable and the cable to the rotation monitor The shields shall be connected to the chassis earth with metal cable nipples The mains cable and the alarm cable do not need to be screened The sc...

Страница 19: ...12 Installation Emotron AB 01 5016 01r0...

Страница 20: ...control board is galvanically isolated from the mains for safety reasons do not make changes while the mains supply is on Fig 10 Control board layout WARNING Always switch off the mains voltage and w...

Страница 21: ...10 VDC supply voltage 7 Common Control signal 11 24 V 24 VDC supply voltage 12 Common Signal ground 15 Common Signal ground Digital inputs 8 DigIn 1 RunL reverse 9 DigIn 2 RunR forward 10 DigIn 3 Not...

Страница 22: ...9 5 4 PREV NEXT ESC ENTER RESET LOC REM 14 20 21 41 42 43 51 52 78 79 Rotation monitor T1 T2 RFI filter 10 VDC AnIn 1 Control signal 10 VDC Common Control signal DigIn 1 RunL DigIn 2 RunR 24 VDC Commo...

Страница 23: ...rent signals 0 10 V 0 24 V 0 4 20 mA which can have only two values high or low and only occa sionally change in value Relay Relay contacts 0 250 VAC can switch highly inductive loads auxiliary relay...

Страница 24: ...ns that in the current circuit for any possible High Frequency HF interference fields no voltage can be induced 4 4 6 Manual control using 10 k potentiometer The drive system can easily be controlled...

Страница 25: ...18 Control Connections Emotron AB 01 5016 01r0...

Страница 26: ...In this example Fig 14 the motor VSD will run with right rotation clockwise To comply with the EMC standard use screened control cables with plaited flexible wire up to 1 5 mm2 or solid wire up to 2...

Страница 27: ...nu level or confirm changed setting step to higher menu level or ignore changed setting step to next menu on the same level step to previous menu on the same level increase value or change selection d...

Страница 28: ...rea E Shows the status of the VSD 3 digits The following status indications are possible Acc Acceleration D ec Deceleration Run Motor runs Tr p Tripped St p Motor is stopped VL Operating at Voltage li...

Страница 29: ...rning Limit No trip RUN green On during 1 second indicating pulse from Rotation monitor 1 Hz Purge 2 Hz Normal Motor speed Motor stopped Run Green Trip Red Power Green Table 7 Function keys ENTER key...

Страница 30: ...ernative 1 When you press the or keys to change a value the cursor is flashing to the left in the display and the value is increased or decreased when you press the appropriate key If you keep the or...

Страница 31: ...ter power up Press Prev for menu O00 Press Enter for menu O10 Press Enter for menu O11 or Press or key to change On to Off Save the changed value by pressing Enter 100 Normal Stp 29 5 rpm A PREV O00 E...

Страница 32: ...changed value by pressing Enter 100 Normal Stp 29 5 rpm A PREV O00 EMX D option Stp ENTER O10 EMX D Pars Stp ENTER ENTER O11 Rot Sensor Stp On NEXT O17 Hold Torque Stp Off NEXT O17 Hold Torque Stp On...

Страница 33: ...26 Operation via the Control Panel Emotron AB 01 01 5016 01r0...

Страница 34: ...application 7 2 1 EMX D Pars 010 Selections and settings of the different parameters for the process Rotation Monitor 011 In this menu set if you have rotation monitor connected or not Gearbox ratio...

Страница 35: ...ransfer function Fig 3 page 7 By setting MCC to On following values will be changed MCC time O19 Time for stand still Default value should normally not be changed Default value 0 0s means continuous M...

Страница 36: ...0 Process Value 711 The process value is a display function showing actual speed of the outgoing shaft Speed 712 Displays the actual motor speed Torque 713 Displays the actual outgoing shaft torque Sh...

Страница 37: ...A Rem Rem TL This means A Parameter Set A is active Rem Reference value comes from terminals 1 22 Rem Run Stop commands come from terminals 1 22 TL Torque Limit active Unit kW Resolution 1 W Unit A Re...

Страница 38: ...tatus of the digital outputs on position 1 DigOut1 2 DigOut2 The status of the associated output is shown 1 High 0 Low The example in Fig 30 indicates that DigOut1 is active and Digital Out 2 is not a...

Страница 39: ...e copied to the trip message log There are nine trip message logs 810 890 When the tenth trip occurs the oldest trip will disappear Trip message 811 81N The information from the status menus are copie...

Страница 40: ...ure trip occurred after 1396 hours and 13 minutes in Run time Fig 34 Trip 3 7 6 2 Reset Trip Log 8A0 Resets the content of the 9 trip memories Default No No 0 Yes 1 NOTE After the reset the setting go...

Страница 41: ...34 Functional Description Emotron AB 01 5016 01r0...

Страница 42: ...solve any problems that arise A variable speed drive is mostly just a small part of a complete VSD system Sometimes it is diffi cult to determine the cause of the failure although the varia ble speed...

Страница 43: ...ed from the variable speed drive Wait at least 5 min utes before continuing 8 2 4 Auto reset Trip If the maximum number of Trips during Auto reset has been reached the trip message hour counter is mar...

Страница 44: ...h mains voltage Check the main supply voltage Try to take away the interference cause or use other main supply lines O ver volt M ains cut Under voltage Too low DC Link voltage Too low or no supply vo...

Страница 45: ...put stage desaturation of IGBTs Check on bad motor cable connections Check on bad earth cable connections Check on water and moisture in the motor housing and cable connections Desat U Desat U Desat V...

Страница 46: ...er Rotation monitor Impulse sensor should be connected General Protection class IP 54 Weight motor unit 9 5 kg control unit 12 5kg Ambient temperature 30 to 40 C Motor size IEC 60034 1 Insulation clas...

Страница 47: ...AB 01 5016 01r0 9 1 Dimensions Fig 36 Dimensions control unit Fig 37 Dimensions motor and gearbox mm 128 5 37 10 396 202 6 416 350 Caution 194 EMX D Gearbox 10 3 1 146 mm EMX D Gearbox 10 3 1 166 mm E...

Страница 48: ...pply voltage 24 VDC 100 mA output 12 Common Signal ground 0 V output 13 AnOut 1 Min speed to max speed 0 10 VDC analogue output 15 Common Signal ground 0 V output 16 DigIn 4 Rotation monitor 0 8 24 VD...

Страница 49: ...42 Technical Data Emotron AB 01 5016 01r0...

Страница 50: ...Tmp 720 Status 721 VSD Status 722 Warning 723 DigIn Status 724 DigOut Status 725 AnIn Status 1 2 726 AnIn Status 3 4 727 AnOut Status 1 2 730 Stored Val 731 Run Time 00 00 00 732 Mains Time 00 00 00...

Страница 51: ...44 Menu List Emotron AB 01 5016 01r0...

Страница 52: ...22 NEXT key 22 PREVIOUS key 22 L LCD display 21 Low Voltage Directive 6 M Machine Directive 6 Main menu 23 Mains supply 10 13 Maintenance 38 Manufacturer s certificate 6 Max motor speed 27 MCC Counte...

Страница 53: ...Emotron AB M rsaregatan 12 SE 250 24 Helsingborg Sweden Tel 46 42 16 99 00 Fax 46 42 16 99 49 E mail info emotron se Internet www emotron com Emotron AB 01 5016 01r0 2010 09 01...

Отзывы: