Installation & Commissioning Instructions
For more information please call us on
01993 824900
or view our website at
www.emmeti.co.uk
Gerpex Press Fit System
Gerpex Press Fit System
2. Installation
All installation must be carried out at temperatures
above -10
o
C and below 45
o
C to avoid any potential
distortion to the materials. In case of temperatures
below 0
o
C, pipe and fittings will need to be stored at
a higher temperature immediately prior to use.
2.1 removal of pipe packaging
• Take care not to damage pipe when removing the
packaging
• Take care not to damage pipe insulation when
removing the packaging
yES
No
2.2 Surface mounted installation
• For surface mounted pipe or pipe installed into
false ceilings/floors and ducts the pipe will need
to be adequately supported at regular intervals
depending on pipe diameter.
• For reference to maximum clip spacing’s please
refer to table 2 and image Fig 2.2
Pipe
dimension
Maximum Distance (S)
for bracketing (cm)
14 x 2
100
16 x 2
100
20 x 2
125
26 x 3
150
32 x 3
200
40 x 3.5
200
50 x 4
250
63 x 4.5
250
S
S
Table 2.
Fig 2.2
A
D
C
A = max 800mm
B = 300mm
C = 300mm
D = max 800mm
B
2.3 Embedded installation
• For embedded installations the pipe must be
securely fastened with ties spaced at the minimum
of 800mm and 300mm either side of bends or
joints, see fig 2.3
• For this type of system it is recommended to use
pre-insulated pipe to minimise heat loss and gain
or to pass through flexible conduit as a minimum
• For surface embedded press fittings we recommend
that the entire fitting in protected from corrosion by
using purpose designed adhesive tapes or expanding
plastic materials that have been adequately sealed.
Fig 2.3