Installation & Commissioning Instructions

For more information please call us on 

01993 824900

 or view our website at 

www.emmeti.co.uk

Gerpex Press Fit System

Gerpex Press Fit System

2. Installation

All installation must be carried out at temperatures 
above -10

o

C and below 45

o

C to avoid any potential 

distortion to the materials. In case of temperatures 
below 0

o

C, pipe and fittings will need to be stored at 

a higher temperature immediately prior to use.

2.1 removal of pipe packaging

•  Take care not to damage pipe when removing the 

packaging

•  Take care not to damage pipe insulation when 

removing the packaging

yES

No

2.2 Surface mounted installation

•  For surface mounted pipe or pipe installed into 

false ceilings/floors and ducts the pipe will need 
to be adequately supported at regular intervals 
depending on pipe diameter.

•  For reference to maximum clip spacing’s please 

refer to table 2 and image Fig 2.2

Pipe 

dimension

Maximum Distance (S) 

for bracketing (cm)

14 x 2

100

16 x 2

100

20 x 2

125

26 x 3

150

32 x 3

200

40 x 3.5

200

50 x 4

250

63 x 4.5

250

S

S

Table 2.

Fig 2.2

A

D

C

A = max 800mm
B = 300mm
C = 300mm
D = max 800mm

B

2.3 Embedded installation

•  For embedded installations the pipe must be 

securely fastened with ties spaced at the minimum 
of 800mm and 300mm either side of bends or 
joints, see fig 2.3

•  For this type of system it is recommended to use 

pre-insulated pipe to minimise heat loss and gain 
or to pass through flexible conduit as a minimum

•  For surface embedded press fittings we recommend 

that the entire fitting in protected from corrosion by 
using purpose designed adhesive tapes or expanding 
plastic materials that have been adequately sealed.

Fig 2.3

Содержание Gerpex Press Fit

Страница 1: ...stallation time Linear expansion similar to copper Minimal tooling required No hot works no permits Less wastage High quality raw materials Stable material costs No scrap value Low heat losses through pipe WRAS approved Easy to transport Double O ring technology www emmeti co uk ...

Страница 2: ...d chilled water systems Please always use the correct tooling and follow the instructions as detailed to ensure correct operation of the system The purpose of these instructions is to ensure that the correct tool selection pipe preparation fitting assembly and installation methods are used 1 Equipment Checks Before Carrying out any work 1 1 Press machine and jaws Please ensure that the jaw pressin...

Страница 3: ...use Please ensure that the jaw size corresponds with the fitting size the pressing machine is in good working order and that the batteries are fully charged ATTENTION If the incorrect sized pressing jaw is used for the fitting you have it will result in an incorrectly pressed fitting and could therefore leak 1 2 Calibration Tools Please ensure that calibration tool has no damage to its face or cut...

Страница 4: ...the pipe will need to be adequately supported at regular intervals depending on pipe diameter For reference to maximum clip spacing s please refer to table 2 and image Fig 2 2 Pipe dimension Maximum Distance S for bracketing cm 14 x 2 100 16 x 2 100 20 x 2 125 26 x 3 150 32 x 3 200 40 x 3 5 200 50 x 4 250 63 x 4 5 250 S S Table 2 Fig 2 2 A D C A max 800mm B 300mm C 300mm D max 800mm B 2 3 Embedded...

Страница 5: ...g data found in table 4 and Fig 2 5 Copper PE X polyethylene mesh PP polypropylene PB polybutylene Steel Inox Steel Gerpex ΔT 10 20 30 40 50 60 70 L ΔL 0 1 0 026 0 052 0 078 0 104 0 130 0 156 0 182 0 2 0 052 0 104 0 156 0 208 0 260 0 312 0 364 0 3 0 078 0 156 0 234 0 312 0 390 0 468 0 546 0 4 0 104 0 208 0 312 0 416 0 520 0 624 0 728 0 5 0 130 0 260 0 390 0 520 0 650 0 780 0 910 0 6 0 156 0 312 0 ...

Страница 6: ...FP L L L L FP SP SP L FP SP L L Ls Ls To allow expansion for pipes installed vertically in shafts or risers with horizontal branches the branch must have a minimum free length LS and the transition through the wall of the shaft should not be sealed so as to allow for movement and the pipe should also be sleeved See Fig 2 9 and 3 0 If the size of the shaft does not allow for the compensation length...

Страница 7: ...t will make calibration difficult 2 8 Pipe preparation Pipe preparation includes calibration and bevelling of the cut end of pipe with a purpose designed tool in readiness for the pipe to be inserted into the fitting Failure to prepare the pipe in this way can lead to damage of the O ring and the possible failure of a fitting To calibrate the pipe the tool must be rotated into the end of the pipe ...

Страница 8: ...Figs 3 7 3 8 and 3 9 Coupling Pipe Pipe out of alignment YES NO NO 2 9 Pipe Fitting Assembly Note Do not lubricate with grease or oil as this can corrode the O rings Please use clean water to lubricate only As the pipe is pushed into the fitting full insertion can be confirmed with the sight hole located in the blue collar See Fig 4 0 Coupling Pipe Pipe out of alignment YES YES NO NO 2 Installatio...

Страница 9: ...ompatible with the Emmeti Gerpex fitting range see diagrams on page 3 and in table 4 Once aligned press and hold the pressing tool trigger until an audible click can be heard this will confirm that a full press has been completed see fig 4 4 Do not attempt to abort a press once started If the machine fails or the battery drains mid press please replace and continue to confirm that the press has be...

Страница 10: ...acilities 5 Testing of the System Gerpex Multi Layer Pipe can also be used with Emmeti developed compression fittings to connect to heating or plumbing manifolds and also to compression fittings including 15 22 and 28mm copper compression These fittings enable the installer to connect to tap connectors isolation valves and radiator valves or to transition onto copper pipe with no requirement for h...

Страница 11: ...ded warranty please provide the below details per project and return to gerpex emmeti co uk Emmeti UK Ltd Unit 6 Tannery Yard Witney Street Burford Oxfordshire OX18 4DQ Upon receipt of a satisfactorily completed form a certificate of warranty will be issued specific to the project in question detailing the 50 year warranty Site Customer Address Installer Contractor Registered Address Invoice Numbe...

Страница 12: ...Emmeti UK 6 Tannery Yard Witney Street Burford Oxfordshire OX18 4DQ T 44 0 1993 824900 F 44 0 1993 824990 W www emmeti co uk E sales emmeti co uk ...

Отзывы: