4.2 Technician Parameters
4.2.1 System
Min
Default Unit
01.03.LCD DISPLAY
(
)
System->LCD display
Max
Language Selection
ENGLISH/TURKISH
0
0(dis)
1
250
23
002.Auto scroll time
003.Auto scroll number
001.Language
Auto Scroll Time
Auto Scroll Number
Scroll Time For Error Messages
2
0
1
0
250
1
Sec
004.Error message scroll time
005.Theme selection
ENGLISH
5
Sec
Notes:
NO / NC : Normally Open / Normally Close
NOR / PULS : Normal / Pulse
dis = disable
Min
Default Unit
01.04.SERIAL COMMUNICATION
(
)
System->Serial Comm.
Max
Slave Address
1
1
247
0
5
3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
001.Slave address
002.Baud rate
Timeout
0(dis)
999
3
005.Timeout
Min
Min
Default
Max
Current Transformer Ratio
Earth Fault CT Ratio
001.CT ratio
002.Earth fault CT ratio
012.PT primary
01 .
3 PT secondary
004.Type of AC system
005.Phase sequence
006.Generator kVA rating
007.Power unit
Unit
01.01.SYSTEM NETWORK
(
)
System->Network
9999
3
9999
65000
480
kVA
1
0
0
50
50
100
1
150
kW
400
400
L123
DISBL, L123, L321
9999
1
100
kVA/kW
Voltage Transformer Primary
Voltage Transformer Secondary
0- 1 Phase 2 Wire
1- 3 Phase 4 Wire
2- 2 Phase 3 Wire L1-L2
3- 2 Phase 3 Wire L1-L3
Phase Sequence
Generator kVA Rating Set
Power Unit
Min
Default
Unit
01.02.BREAKERS
(
)
System->Breakers
Max
Gen. Close Breaker Contact Type
Gen. Close Breaker Relay Type
Gen. Close Timer
0
Gen. Open Breaker Relay Type
0
3
Gen. Open Timer
NO / NC
NO
NOR / PULS
5
1
250
0
Sec
0
NOR / PULS
0.5
0.5
1
0.0
0.0
250
10.0
10.0
5
3
0
0
250
250
2
5
5.0
Breaker Close Pulse Time
Breaker Open Pulse Time
Transfer Time
Spring Loading Time
Retry Number
Neutral Contactor Fail Delay
002.Gen.close breaker cont.type
003.Gen.close breaker relay type
004.Generator close timer
005.Gen.open breaker relay type
006.Generator open timer
001.Type of Breaker
013.Breaker open pulse time
014.Transfer time
015.Spring loading time
016.Retry number
017.Neutral contactor control
018.Neutral contactor fail delay
012.Breaker close pulse time
Sec
Sec
Sec
Sec
Sec
1
0.0
250
25.0
Sec
Neutral Contactor Control:
0-DISABLE, 1-EACH or 2-COMMON
0
0
2
Hardware Breaker Selection:
0-Breakers
1-User Configured
2-Motorised Breakers (Compact Type)
3-Motorised Breakers (Open Type)
Theme Selection:
0-Black theme, 1-Gray theme
V
V
V
V