15
Note:
dis = disable
Min
Default Unit
04.06.CANBUS ERROR SET
(
)
Engine->CanBus error set
Max
Can Fault Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
0
0
2
0
0(dis)
4
002.CAN fault activation
001.CAN fault actions
Sec
Can Fault Delay
10
3 250
003.CAN fault delay
Can Fault Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Amber Warning Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
2
0
2
0
0(dis)
4
005.Amber warning activation
004.Amber warning actions
Sec
J1939 Amber Warning Lamp Delay
2
0 250
006.Amber warning delay
J1939 Amber Warning Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active
J1939 Red Stop Lamp Actions:
0- Disable
1- Warning Non-Latching
2- Warning
3- Electrical Trip
4- Shutdown
2
0
2
0
0(dis)
4
008.Red stop activation
007.Red stop actions
Sec
J1939 Red Stop Lamp Delay
2
0 250
009.Red stop delay
J1939 Red Stop Lamp Activation:
0- Active From Starting
1- Active From Safety On
2- Always Active