30
Min
Default Unit
09.02.AVR CONTROL (Synchronization
)
->AVR control
Max
400
37.5
62.5
50.0
0
3.24
0.30
0.01
300
5
5.00
60
0.0
0.0
0.0
0
0.00
0.00
0.00
60
0
1.00
002.Manual voltage set
003.Minimum output value
004.Maximum output value
005.Initial value
006.Output direction
007.Proportional
008.Integral
009.Derivative
010.Voltage control start
011.Voltage control delay
012.Voltage control ramp
Manual
Set
Voltage
Minimum Output Value
Maximum Output Value
Initial Output Value
Proportional
Integral
Derivative
Voltage Control Start Value
Voltage Control Start Delay
Voltage Control Ramp Value
440
100.0
100.0
100.0
1
99.99
99.99
99.99
440
999
99.99
%
%
%
%/s
V
V
V
V
013.Maximum output limit actions
014.Max.output limit act.dely time
015.Voltage control droop
0(dis)
0
3
99
0(dis)
2 Sec
Max. Output Limit
.
Act Delay Time
Voltage Control Droop
Maximum Output Limit
:
0-
, 1-
,
2-
, 3-
Actions
Disable
Warning
Electrical Trip
Shutdown.
0.0
20.0
0.0
%
0- Positive
1- Negative
001.Voltage control
Voltage Control Selection:
0- Disable
1- Analogue
2- Digital (Up/Down)
1
0
2
016.Up/Down pulse period
017.Up/Down pulse time
018.Up/Down voltage deadband
0.1
0.01
0.10
10.0
5.00
9 9
.9
1.0
0.50
1.00
Sec
Sec
%
Voltage Up/Down Pulse Period
Voltage Up/Down Pulse Time
Up/Down Voltage Deadband
019.Up/Down voltage rate
0.01 9
9
9.9
0.70 %/s
Up/Down Voltage Rate
Min
Default Unit
09.03.PF CONTROL (Synchronization
)
->PF control
Max
3.24
0.30
0.01
3.00
0.00
0.00
0.00
0 1
.0
001.PF control
002.Proportional
003.Integral
004.Derivative
005.PF control ramp
Power Factor Control
Proportional
Integral
Derivative
PF Control Ramp Value
99.99
99.99
99.99
99.99
%/s
DISBL
ENABL/DISBL
Sec
Sec
Min
09.04.CANOPEN CONTROL (
)
Synchronization->CANOPEN control
1
4
0.10
1.00
1
0
0.10
0.01
001.Device number
002.Baudrate
003.Message transmission rate
004.Data delay time
005.Can Open fault actions
Device Number
Message Transmission Rate
Data Delay Time
32
7
0.30
99.99
Baud Rate: 0 - 20
1 - 50
2 - 100
3 - 125
4 - 250
5 - 500
6 - 800
7 - 1000
kBaud
Default
Max
Unit
0(dis)
2
2
Can Open Fault
:
0-
1-
2-
Actions
Disable
Warning
Electrical Trip
006.Check Can Open version
Check Can Open version
ENABL
ENABL/DISBL