23
Note:
dis = disable
Min
Default Unit
05.15.CONF. INPUT-13
(
)
Inputs->Conf. input-13
Max
3
0(dis)
1
0
4
2
0
0
250
0
Sec
0
001.Input type
002.Polarity
003.Indication
004.Activation
005.Select from list
006.Active delay
0- Disable
1- User Configured (Digital)
2- Select From List (Digital)
3- Cabin Temperature (Anolog)
If Input Type is Digital
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If Input Type is User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If Input Type is User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
Input active delay (If Input Type is Digital)
If Input Type is Select From List
0-Remote Start On Load
1-Remote Start Off Load
2-Reserved
3-Maintenance Alarm Reset
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-Generator Closed Auxiliary
12-Generator Load Inhibit
13-Reserved
14-Neutral contactor feedback
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Runs(Exercise) Inhibited
19-Top priority
20-Generator Breaker Close
21-Generator Breaker Open
22-Remote Inhibit
23-Being Found Alive
24-Unconditional Synchron
25-Remote Speed Up
26-Remote Speed Down
27-Remote Voltage Up
28-Remote Voltage Down
dis
007.Cabin temp.low prealr
008.Cabin temp.low reset
009.Cabin temp.low shutd.
010.Cabin temp.high preal
011.Cabin temp.high reset
012.Cabin temp.high shutd
5
Cabin temperature low prealarm
Cabin temperature low prealarm reset
Cabin temperature low shutdown
Cabin temperature high prealarm
Cabin temperature high prealarm reset
Cabin temperature high shutdown
100
100
100
100
100
100
ºC
ºC
ºC
ºC
ºC
ºC
dis
0
dis
dis
0
dis
-50(dis)
-50
-50(dis)
-50(dis)
-50
-50(dis)
0
0
2
28
18