25
4.2.5 Outputs
Min
Default Unit
06.01.CONF. OUTPUT-1
(
)
Outputs->Conf. output-1
Max
0
1
0
167
0
49
001.Polarity
002.Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-CAN ECU POWER
10-CAN ECU STOP
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH ALARM
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT-1 ALARM
24-DIGITAL INPUT-2 ALARM
25-DIGITAL INPUT-3 ALARM
26-DIGITAL INPUT-4 ALARM
27-DIGITAL INPUT-5 ALARM
28-DIGITAL INPUT-6 ALARM
29-DIGITAL INPUT-7 ALARM
30-DIGITAL INPUT-8 ALARM
31-DIGITAL INPUT-9 ALARM
32-DIGITAL INPUT-10 ALARM
33-DIGITAL INPUT-11 ALARM
34-DIGITAL INPUT-12 ALARM
35-DIGITAL INPUT-13 ALARM
36-EXPANSION INPUT-1 ALARM
37-EXPANSION INPUT-2 ALARM
38-EXPANSION INPUT-3 ALARM
39-EXPANSION INPUT-4 ALARM
40-EXPANSION INPUT-5 ALARM
41-EXPANSION INPUT-6 ALARM
42-EXPANSION INPUT-7 ALARM
43-EXPANSION INPUT-8 ALARM
44-EARTH FAULT
45-EMERGENCY STOP
46-FAIL TO START ALARM
47-FAIL TO STOP ALARM
48-CONF. AI1 CONTROL
49-FUEL RELAY ENERGISED
50-GAS ENGINE IGNITION OUTPUT
51-GENERATOR AT REST
52-GENERATOR AVAILABLE
53-GENERATOR CLOSED AUXILIARY
54-GENERATOR FAILED TO CLOSE
55-GENERATOR FAILED TO OPEN
56-GENERATOR HIGH FREQUENCY PRE-ALARM
57-GENERATOR HIGH FREQUENCY ALARM
58-GENERATOR HIGH VOLTAGE PRE-ALARM
59-GENERATOR HIGH VOLTAGE ALARM
60-GENERATOR LOAD INHIBIT
61-GENERATOR LOW FREQUENCY PRE-ALARM
62-GENERATOR LOW FREQUENCY ALARM
63-GENERATOR LOW VOLTAGE PRE-ALARM
64-GENERATOR LOW VOLTAGE ALARM
65-GENERATOR STOPPING
66-GENERATOR OPEN BREAKER
67-HORN OUTPUT LATCHED
68-HORN OUTPUT PULSED
69-LAMP TEST
70-CONF. AI2 CONTROL
71-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
72-LOW TEMPERATURE
73-MAINTENANCE DUE ALARM
74-
75-
76-
77-
78-
79-
80-
81-
82-
83-
FAIL
84-NO LOADING COMMAND
85-OIL PRESSURE LOW PRE-ALARM
86-OIL PRESSURE LOW ALARM
87-CONF.AI1.HIGH PRE A
88-CONF.AI1.HIGH ALARM
89-OVER CURRENT PRE-ALARM
90-OVER CURRENT
91-OVER POWER PRE-ALARM
92-OVER POWER ALARM
93-OVERSPEED PRE-ALARM
94-OVERSPEED SHUTDOWN
95-PANEL LOCK
96-PRE-HEAT(during preheat timer)
97-PRE-HEAT(until end of cranking)
98-PRE-HEAT(until end of warming)
99-PRE-HEAT(until end safety on)
5-RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
NEUTRAL CONTACTOR CONTROL
RESERVED
RESERVED
NEUTRAL CONTACTOR
- LARM