WLCA/WLHA High Wall Evaporator

22

Table #1 – ConfiGUrAtion modE

sEttinG itEm

LCd titLE 

dispLAy

possiBLE VALUE 

(flashing)

fACtory 

sEttinGs

1

 Temperature scale

“01 F-C”

“F” 

Fahrenheit 

“F”

 

“C”

 Celsius

2

Remote wall thermostat mode 

(pg. 21)

“02 r – t”

“ON”

 Remote wall thermostat on

“OFF”

“OFF

Remote wall thermostat off

3

Heat Source (pg. 17)

“03 HEAT”

“ON” 

Heat source available

“ON”  If El. 

heat 

“OFF”

Not available

“OFF” If no 

El. Ht.

4

Heat pump (This setting is 

skipped if Heat source setting 

is “Off”)(pg.17)

“04 H-P”

“ON” 

Heat pump available

“OFF” 

“OFF” 

Not available

5

Auto-changeover differential 

(This setting is skipped if Heat 

source setting is “Off”or if 

remote setting is “On”)(pg.18)

“05 d-b”

Between “2° – 6°”

“2” 

6

Check filter time (pg.19)

“06 F:Lt”

“2”

 250 hours

“10”

“5”

 500 hours

“7”

 750 hours

“10”

1000 hours

“12”  

1250 hours

7

Room air sampling (pg. 20)

“07 A:r”

“OFF”

 Disabled

“15”

“5” 

5 minutes

“10”

 10 minutes

“15”

15 minutes

8

Annunciation (pg. 23)

“08 b-P”

“ON” 

Enabled

“ON””

“OFF”

 Disabled

9

LCD Backlight (pg. 23)

 

“09 L:tE”

“ON”

 Always on

 “In

“In” 

Intermittent

“OFF” 

Always off

Louver position (pgs. 16 & 17)

“Lou”

01, 02, 03, 04, 05, 06 and Auto

 “01”

Test Mode (pgs. 16 & 22)

“tSt”

“tSt”

Off

room Air sampling

  In the auto (cycling) fan mode Room 

Air Sampling will automatically cycle the 

fan on for a minimum of 60 seconds, with 

the control in the satisfied state, to peri

-

odically circulate room air. Room air strati

-

fication is therefore minimized due to the 

fan being off for long periods of time so 

that  the  microprocessor  may  accurately 

track room temperature.

  Room air sampling must be selected 

through  the  configuration  mode.  Select

-

able sampling times are: “OFF” (disabled), 

5 min, 10 min, and 15 min.

Configuration Mode

  While  the  unit  is  in  the  Off  mode, 

pressing  the  “MODE”  and  “PROG”  but

-

tons  simultaneously  for  10  seconds  will 

enter  the  Configuration  mode.  While  in 

Configuration mode, pressing the MODE” 

and  “PROG”  buttons  simultaneously 

again or left idle for 20 seconds, will save 

the new settings and exit the Configura

-

tion mode.

  The following table specifies the user se

-

lectable settings in the Configuration mode:

 sEqUEnCE of opErAtion – Unit moUntEd KEy pAd modE

Содержание AmericaSeries WLC30

Страница 1: ...l LLC 5780 Success Dr Rome NY 13440 www enviromaster com installation operation and maintenance MANUAL An ISO 9001 2000 Certified Company WLC WLH Straight Cool Heat Pump Nominal Circuit Capacities WLH...

Страница 2: ......

Страница 3: ...oltage shown is the same as the electric supply to the unit The EMI AmericaSeries evaporator must be connectedonlytoaproperly grounded electrical supply Do not fail to properly ground this unit Turn o...

Страница 4: ...y in Auto Fan Mode to help eliminate room temperature stratification Selectable Fahrenheit F or Celsius C temperature scale Dry mode Operates cooling and electric heat simultaneously to remove humidit...

Страница 5: ...ble washable reusable nylon mesh filter Horizontal discharge louver construct ed of high temperature ABS plastic that can be set to oscillate or can be parked in six pre set positions Manually adjusta...

Страница 6: ...mounting slot on the back of the unit over the bracket and make certain it fits properly Note Panels should remain on the unit at all times while powered and in opera tion Service should be performed...

Страница 7: ...nd electrical wiring This entails removal of three screws Locate Electrical Wiring for the proper wire and breaker or time delay fuse size 4 Inspect the existing wiring for any defects such as cut or...

Страница 8: ...Wires designated Y yellow and C brown of the air handler should be con nected to the corresponding Y yellow and C brown wires or terminals of the condenser See Figure 1A Other wires or terminals such...

Страница 9: ...igure 1A and figure 1B for unit mounted controls The 24V control transformer is located in the air handler unit This provides low volt control power to both the air handler and condenser Depending on...

Страница 10: ...case ensure that any unused wires are insulated with a wire nut to prevent them from mak ing contact with the junction box or other metal surfaces If the indoor unit has electric heat then a W connect...

Страница 11: ...connections Once the unit is mounted and level the WLC WLH piping connections can be made by removing the left end cap and bottom panel 1 Remove the Philips head screws on bottom of unit and lift bot...

Страница 12: ...n any WLH24 evaporator is matched with a S1C8000 or S1H8000 condenser which has an 18 000 Btuh compressor 8 in the capacity decoding field The piston will need replacement only on the 18 000 Btuh zone...

Страница 13: ...ing 3 We recommend the use of a shield can be made from some scrap metal to protect the paint 4 Braze tubing into fittings 5 Attach manifold set 6 Evacuate line to 500 microns or less to ensure all mo...

Страница 14: ...hg Ft Factory Charge S1H9 WLH09 25 oz 41 oz S1H2 WLH12 25 oz 44 oz S1H8 WLH24 56 oz 53 oz S1H4 WLH24 56 oz 67 oz 8 Charge to proper weight charge based on your feet of interconnect see below Note Char...

Страница 15: ...e order shown below 1 Replace the bottom panel 2 Fasten the right end cap side first with the Philips head screw 3 Next replace and tighten the re maining screws across the bot tom panel 4 Replace lef...

Страница 16: ...ultaneously for 3 sec 7 Day Prog mode Press PROG TIME buttons again or if left idle for 20 sec exit 7 Day prog mode Configuration Mode in Off mode press MODE PROG buttons simultaneously for 10 sec Con...

Страница 17: ...e constantly at low speed Auto fan mode is not available in Fan only Dry and Remote wall thermostat modes PROG The PROG button is used to enter or exit the Pre program Run mode The Pre program Run mod...

Страница 18: ...unit is turned on via the ON OFF button the louver will open and oper ate according to the setting selected in the Louver Configuration mode To enter the Louver Configuration mode press and hold the F...

Страница 19: ...tempera ture will be displayed Press either the Up or Down arrow buttons to change the setpoint temperature The setpoint tem perature will change by one degree with each successive press of the Up or...

Страница 20: ...grees the compressor will stop and heating will continue to boost the room temperature back up to setpoint temperature If the room temperature rises above the setpoint tem perature by two degrees hea...

Страница 21: ...k While in 7 day programming select the day to be copied Then press the FAN and PROG buttons simultaneously for three seconds The selected day will be copied to the rest of the week Sequence of Operat...

Страница 22: ...D Backlight pg 23 09 L tE ON Always on In In Intermittent OFF Always off Louver position pgs 16 17 Lou 01 02 03 04 05 06 and Auto 01 Test Mode pgs 16 22 tSt tSt Off Room Air Sampling In the auto cycli...

Страница 23: ...of Operation Wall mounted thermostat mode For Wall mounted thermostat op eration the control must be configured through the Configuration mode Be sure to select Remote ON in the configura tion menu Se...

Страница 24: ...erature The outdoor condenser will stop The fan will operate as described in Fan Operation Note Once the cooling has cycled off or following a power outage the com pressor will not start for at least...

Страница 25: ...me pre vents either the compressor or heat source from cycling off prematurely The minimum ON time for both the compressor and electric heat is two minutes Minimum on time is available only while the...

Страница 26: ...condition exists continuously for three minutes the LCD will display error code E03 to signify that a fault has occurred The compressor will switch off for a mini mum of three minutes and until the fa...

Страница 27: ...eperation for Start Up Remove any tools or other obstructions Be sure the filter is in place Verify that the unit is level separate anylinesthatcontacteachother replace the cabinet end cap and the gri...

Страница 28: ...t Unit Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving...

Страница 29: ...air intake access grille Lift and remove grille 2 To clean the filter pull open the 2 clips at the base of the filter and carefully pull the filter out Place the filter on a flat surface a To vacuum U...

Страница 30: ...ave the full model and serial number available prior to calling EMI America Series evaporators are designed to operate with EMI America Series condensers The evaporator indoor unit and condenser outdo...

Страница 31: ...ting plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should also be made By placing a voltmeter across low volt terminals R and C at the indoor unit the...

Страница 32: ...eature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur Each electric heat assembly is al...

Страница 33: ...Y and C Check to see that the amp draw corresponds with the electric heat rating The following current values apply when the unit is connected to a 230V power supply These values include indoor fan m...

Страница 34: ...pump is not clearing or the switch may be bad Troubleshooting procedure Continued Frequently asked questions Q The display on the indoor unit is blank What should I do A Check the power supply see Pow...

Страница 35: ...e clean and free of dirt A dirty filter will reduce airflow and efficiency Also check that the coil is clean If the coil is dirty then it should be cleaned using an appropriate coil cleaner or mild de...

Страница 36: ...A B C D E 5 1 2 4 WLC WLH OBSERVED SOUND VALUES 230V High Speed Fan Model dBA 09 12 45 18 24 56 30 36 60 WLC WLH PHYSICAL DIMENSIONS Model A Depth B Height C Length D Mounting Bracket Clearance E Tubi...

Страница 37: ...is provided to transition to 3 4 O D interconnect WLC WLH ELECTRICAL SPECIFICATIONS MODEL VOLTS HZ PH FAN RLA HP HEATER K W AMPS TOTAL AMPS MIN VOLT M C A HACR BRKR SMALL CABINET 09 12 09 12 115 60 1...

Страница 38: ...and efficiency Installation of this product should follow the manufacturer s refrigerant charging and air flow instructions Failure to confirm proper charge and airflow may reduce energy efficiency an...

Страница 39: ...Unit s Condenser Btuh SEER SHR EER Ref WLH09 WLH24 T3C994 41 000 13 77 11 9 R22 WLH09 T3C999 27 000 13 80 11 7 R22 WLH12 T3C222 34 000 13 71 11 7 R22 WLH09A WLH24 T3C928 39 000 13 77 11 9 R22 WLH09 WL...

Страница 40: ...e Zone Side Discharge S2C Dual Zone Side Discharge WLC WLH High Wall Air Handler UNC UNH Universal Floor or Ceiling Air Handler CAC CAH Cassette Air Handler T2C T3C and T4C 2 3 and 4 Zone Top Discharg...

Отзывы: