background image

www.enviromaster.com

WLCA/WLHA High Wall Evaporator

20

between  room  temperature  and  setpoint 

temperature is less than two degrees. At 

that  time  the  electric  heat  will  switch  off 

and the heat pump (compressor) will take 

over  the  heating  demand.  The  electric 

heater will not re-start until a three minute 

delay  has  elapsed.  Once  the  room  tem

-

perature  is  satisfied  and  the  two-minute 

minimum run time has elapsed, the com

-

pressor will cycle off. The compressor will 

not re-start until a three minute delay has 

elapsed. The fan will operate as described 

in “Fan Operation”.

dry mode

  For 

dry mode

 operation the unit must 

have  an  electric  heater. Also  the  control 

must  first  be  configured  properly  (Heat 

source – “ON”). See: Configuration Inter

-

face mode. 

  Dry  mode  will  remove  humidity  from 

the air while maintaining a specific setpoint 

temperature. This is done by energizing the 

compressor in cooling along with the electric 

heater. Dry mode will not maintain a specific 

humidity level. The unit must be equipped 

with an optional electric heat element.

  For Dry Mode operation, first turn the 

unit on via the ON/OFF button. Select Dry 

mode  via  the  MODE  button.  The  room 

temperature and setpoint temperature will 

be displayed. Press either the Up or Down 

arrow buttons to change the setpoint tem

-

perature.  The  setpoint  temperature  will 

change by one degree with each succes

-

sive press of the Up or Down arrow but

-

tons. Holding the button in will change the 

temperature rapidly.

  Place  the  setpoint  temperature  at  a 

desired room temperature. Depending on 

the difference between room temperature 

and setpoint temperature the compressor 

and/or  heat  source  will  energize.  If  the 

room temperature and setpoint tempera

-

ture are the same the compressor will op

-

erate in cooling and the electric heat will 

also energize.

  Should the room temperature fall be

-

low  the  setpoint  temperature  by  two  de

-

grees, the compressor will stop and heating 

will continue to boost the room temperature 

back up to setpoint temperature. If the room 

temperature rises above the setpoint tem

-

perature by two degrees, heating will stop 

and cooling will continue to bring the room 

temperature back down to setpoint temper

-

ature. The fan will operate continuously at 

low speed while in Dry Mode.

  In order to prevent short cycling there 

is a two minute minimum on time for both 

cooling and heating. The minimum off time 

is 3 minutes. Also there is a 30 second de-

lay  between  the  start  of  the  compressor 

and the start of the heat source. 

Auto Changeover mode

  For 

Auto  Changeover  mode

  (ACO) 

the unit must have a heat source. Also the 

control  must  first  be  configured  properly 

(Heat source – “ON”). See: Configuration 

Interface mode.

  Auto  Changeover  mode  will  operate 

either  Cooling  mode  or  Heating  mode. 

The control will select the mode of opera

-

tion depending on the setpoint tempera

-

ture, room temperature and the differen

-

tial  setting  selected  in  the  Configuration 

mode (See Configuration mode).

  For Auto Changeover mode, first turn 

the unit on via the ON/OFF button. Select 

Auto mode via the Mode button. The room 

temperature and setpoint temperature will 

be displayed. Press either the Up or Down 

arrow buttons to change the setpoint tem

-

perature.  The  setpoint  temperature  will 

change by one degree with each succes

-

sive press of the Up or Down arrow but

-

tons. Holding the button in will change the 

temperature rapidly.

 

Place  the  setpoint  temperature  be

-

low  the  room  temperature  by  the  dead 

band  amount  selected  in  the  configura

-

tion mode. The compressor will start and 

the unit will run cooling operation as de

-

scribed under “Cool Mode”.

  If  the  set  point  temperature  is  above 

the room temperature by the dead band 

amount  selected  in  the  configuration 

mode, the unit will run heating operation 

as described under “Heat Mode” 

set time mode

  The  “TIME”  button  is  used  to  enter 

or exit the Set Time mode. The Set Time 
mode can be entered while the control is in 

 sEqUEnCE of opErAtion – Unit moUntEd KEy pAd modE

Содержание AmericaSeries WLC30

Страница 1: ...l LLC 5780 Success Dr Rome NY 13440 www enviromaster com installation operation and maintenance MANUAL An ISO 9001 2000 Certified Company WLC WLH Straight Cool Heat Pump Nominal Circuit Capacities WLH...

Страница 2: ......

Страница 3: ...oltage shown is the same as the electric supply to the unit The EMI AmericaSeries evaporator must be connectedonlytoaproperly grounded electrical supply Do not fail to properly ground this unit Turn o...

Страница 4: ...y in Auto Fan Mode to help eliminate room temperature stratification Selectable Fahrenheit F or Celsius C temperature scale Dry mode Operates cooling and electric heat simultaneously to remove humidit...

Страница 5: ...ble washable reusable nylon mesh filter Horizontal discharge louver construct ed of high temperature ABS plastic that can be set to oscillate or can be parked in six pre set positions Manually adjusta...

Страница 6: ...mounting slot on the back of the unit over the bracket and make certain it fits properly Note Panels should remain on the unit at all times while powered and in opera tion Service should be performed...

Страница 7: ...nd electrical wiring This entails removal of three screws Locate Electrical Wiring for the proper wire and breaker or time delay fuse size 4 Inspect the existing wiring for any defects such as cut or...

Страница 8: ...Wires designated Y yellow and C brown of the air handler should be con nected to the corresponding Y yellow and C brown wires or terminals of the condenser See Figure 1A Other wires or terminals such...

Страница 9: ...igure 1A and figure 1B for unit mounted controls The 24V control transformer is located in the air handler unit This provides low volt control power to both the air handler and condenser Depending on...

Страница 10: ...case ensure that any unused wires are insulated with a wire nut to prevent them from mak ing contact with the junction box or other metal surfaces If the indoor unit has electric heat then a W connect...

Страница 11: ...connections Once the unit is mounted and level the WLC WLH piping connections can be made by removing the left end cap and bottom panel 1 Remove the Philips head screws on bottom of unit and lift bot...

Страница 12: ...n any WLH24 evaporator is matched with a S1C8000 or S1H8000 condenser which has an 18 000 Btuh compressor 8 in the capacity decoding field The piston will need replacement only on the 18 000 Btuh zone...

Страница 13: ...ing 3 We recommend the use of a shield can be made from some scrap metal to protect the paint 4 Braze tubing into fittings 5 Attach manifold set 6 Evacuate line to 500 microns or less to ensure all mo...

Страница 14: ...hg Ft Factory Charge S1H9 WLH09 25 oz 41 oz S1H2 WLH12 25 oz 44 oz S1H8 WLH24 56 oz 53 oz S1H4 WLH24 56 oz 67 oz 8 Charge to proper weight charge based on your feet of interconnect see below Note Char...

Страница 15: ...e order shown below 1 Replace the bottom panel 2 Fasten the right end cap side first with the Philips head screw 3 Next replace and tighten the re maining screws across the bot tom panel 4 Replace lef...

Страница 16: ...ultaneously for 3 sec 7 Day Prog mode Press PROG TIME buttons again or if left idle for 20 sec exit 7 Day prog mode Configuration Mode in Off mode press MODE PROG buttons simultaneously for 10 sec Con...

Страница 17: ...e constantly at low speed Auto fan mode is not available in Fan only Dry and Remote wall thermostat modes PROG The PROG button is used to enter or exit the Pre program Run mode The Pre program Run mod...

Страница 18: ...unit is turned on via the ON OFF button the louver will open and oper ate according to the setting selected in the Louver Configuration mode To enter the Louver Configuration mode press and hold the F...

Страница 19: ...tempera ture will be displayed Press either the Up or Down arrow buttons to change the setpoint temperature The setpoint tem perature will change by one degree with each successive press of the Up or...

Страница 20: ...grees the compressor will stop and heating will continue to boost the room temperature back up to setpoint temperature If the room temperature rises above the setpoint tem perature by two degrees hea...

Страница 21: ...k While in 7 day programming select the day to be copied Then press the FAN and PROG buttons simultaneously for three seconds The selected day will be copied to the rest of the week Sequence of Operat...

Страница 22: ...D Backlight pg 23 09 L tE ON Always on In In Intermittent OFF Always off Louver position pgs 16 17 Lou 01 02 03 04 05 06 and Auto 01 Test Mode pgs 16 22 tSt tSt Off Room Air Sampling In the auto cycli...

Страница 23: ...of Operation Wall mounted thermostat mode For Wall mounted thermostat op eration the control must be configured through the Configuration mode Be sure to select Remote ON in the configura tion menu Se...

Страница 24: ...erature The outdoor condenser will stop The fan will operate as described in Fan Operation Note Once the cooling has cycled off or following a power outage the com pressor will not start for at least...

Страница 25: ...me pre vents either the compressor or heat source from cycling off prematurely The minimum ON time for both the compressor and electric heat is two minutes Minimum on time is available only while the...

Страница 26: ...condition exists continuously for three minutes the LCD will display error code E03 to signify that a fault has occurred The compressor will switch off for a mini mum of three minutes and until the fa...

Страница 27: ...eperation for Start Up Remove any tools or other obstructions Be sure the filter is in place Verify that the unit is level separate anylinesthatcontacteachother replace the cabinet end cap and the gri...

Страница 28: ...t Unit Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving...

Страница 29: ...air intake access grille Lift and remove grille 2 To clean the filter pull open the 2 clips at the base of the filter and carefully pull the filter out Place the filter on a flat surface a To vacuum U...

Страница 30: ...ave the full model and serial number available prior to calling EMI America Series evaporators are designed to operate with EMI America Series condensers The evaporator indoor unit and condenser outdo...

Страница 31: ...ting plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should also be made By placing a voltmeter across low volt terminals R and C at the indoor unit the...

Страница 32: ...eature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur Each electric heat assembly is al...

Страница 33: ...Y and C Check to see that the amp draw corresponds with the electric heat rating The following current values apply when the unit is connected to a 230V power supply These values include indoor fan m...

Страница 34: ...pump is not clearing or the switch may be bad Troubleshooting procedure Continued Frequently asked questions Q The display on the indoor unit is blank What should I do A Check the power supply see Pow...

Страница 35: ...e clean and free of dirt A dirty filter will reduce airflow and efficiency Also check that the coil is clean If the coil is dirty then it should be cleaned using an appropriate coil cleaner or mild de...

Страница 36: ...A B C D E 5 1 2 4 WLC WLH OBSERVED SOUND VALUES 230V High Speed Fan Model dBA 09 12 45 18 24 56 30 36 60 WLC WLH PHYSICAL DIMENSIONS Model A Depth B Height C Length D Mounting Bracket Clearance E Tubi...

Страница 37: ...is provided to transition to 3 4 O D interconnect WLC WLH ELECTRICAL SPECIFICATIONS MODEL VOLTS HZ PH FAN RLA HP HEATER K W AMPS TOTAL AMPS MIN VOLT M C A HACR BRKR SMALL CABINET 09 12 09 12 115 60 1...

Страница 38: ...and efficiency Installation of this product should follow the manufacturer s refrigerant charging and air flow instructions Failure to confirm proper charge and airflow may reduce energy efficiency an...

Страница 39: ...Unit s Condenser Btuh SEER SHR EER Ref WLH09 WLH24 T3C994 41 000 13 77 11 9 R22 WLH09 T3C999 27 000 13 80 11 7 R22 WLH12 T3C222 34 000 13 71 11 7 R22 WLH09A WLH24 T3C928 39 000 13 77 11 9 R22 WLH09 WL...

Страница 40: ...e Zone Side Discharge S2C Dual Zone Side Discharge WLC WLH High Wall Air Handler UNC UNH Universal Floor or Ceiling Air Handler CAC CAH Cassette Air Handler T2C T3C and T4C 2 3 and 4 Zone Top Discharg...

Отзывы: