WLCA/WLHA High Wall Evaporator
rEfriGErAnt pipinG
The WLC/WLH is equipped with a
Flo-Rater/Piston Expansion device. Con
-
nections are sweat type.
The suction line (large) must be insulated
the entire length with closed cell, foam tube
insulation. Do not insulate the liquid line
(small). Connect the outdoor unit according
to the instructions supplied with unit.
All horizontal piping runs must be level and
without dips to trap the oil.
pipinG do’s And don’ts
• Avoid piping on a rainy day.
• Use refrigerant grade copper tubing.
• Use a tubing bender and avoid unnec
-
essary bending.
• Cap ends of lines until ready for final
connections.
Once the unit is mounted and level
the WLC/WLH piping connections can be
made by removing the left end cap and
bottom panel:
1. Remove the Philips-head
screws on bottom of
unit and lift bottom
panel off.
2. Exposed piping and condensate drain
connections. (S
ee table on page 36 for
connection size per unit capacity.)
s
uction line
Liquid line
c
ondensate drain
When matching a the WLH24 with an 18,000
Btuh condenser circuit, the interconnecting
suction line needs to be 5/8” O.D. to match
the condenser service valve connection.
Therefore the 3/4” O.D. suction connection
of the WLH24 unit needs to be reduced to
5/8” at the WLH24 unit connection.
note:
The left end cap must
be removed prior to remov
-
ing the bottom.
f
ollow the
instructions on page 6 for
removing the end cap.
WLC/WLH HiGH WALL EVAporAtor instALLAtion instrUCtions