www.enviromaster.com
Side Discharge Condensers
7
inStallation inStrUCtionS
10. T
o replace side panel slide the slotted
holes of the panel onto the loosened
screws of the front panel so that the
edge of the front panel covers the edge
of the side panel.
eleCtriCal Wiring
Continued
11. Fasten all remaining loose screws.
reFrigerant piping
The system will support refriger
-
ant runs to the inside unit of up to 100'
equivalent feet with a 35' rise included.
The units are furnished with sweat con
-
nections and are equipped with refrigerant
valves and Schrader fittings for charging
and taking pressure readings. The follow
-
ing precautions should be made:
• Be certain no burrs remain on the
fittings.
• Use only clean refrigeration tubing.
• Use tube benders to guard against
kinking.
• Avoid piping on wet and rainy days
and
insulate suction line
. Be certain
that plastic end caps remain in place
when inserting through wall openings.
Isolate tubing from transmitting vibra
-
tion to the building or unit and avoid
contact with sharp edges.
refrigera-
tion valves should be wrapped with
a wet rag "heat sink" to protect
valves while brazing.
note:
It is recommended that a
filter drier be installed in liquid line, at
the indoor unit on models that a filter
drier is not already factory installed
(i.e. 18K and larger).
interConneCting tUbing
SpeCiFiCationS
S1
model
maX.
length
max.
lift
liquid
line o.D.
Suction
line o.D.
09
100’
35’
1/4"
1/2"
12
100’
35’
1/4"
1/2"
18
100’
35’
3/8"
5/8"
24
100’
35’
3/8"
3/4"
30
100’
35’
3/8"
3/4"
36
100’
35’
3/8"
3/4"
S2C tUbing SpeCiFiCationS
Circuit
Size
line Sizes o.D.
liquid
Suction
09, 12
1/4”
1/2”
Содержание AmericaSeries S1C2
Страница 12: ...www enviromaster com Side Discharge Condensers 12 SINGLE ZONE OPERATION CHARTS...
Страница 13: ...www enviromaster com Side Discharge Condensers 13 SINGLE ZONE OPERATION CHARTS...
Страница 14: ...www enviromaster com Side Discharge Condensers 14 SINGLE ZONE OPERATION CHARTS...
Страница 15: ...www enviromaster com Side Discharge Condensers 15 SINGLE ZONE OPERATION CHARTS...
Страница 16: ...www enviromaster com Side Discharge Condensers 16 SINGLE ZONE Heat Pump OPERATION CHARTS...
Страница 17: ...www enviromaster com Side Discharge Condensers 17 SINGLE ZONE Heat Pump OPERATION CHARTS...
Страница 18: ...www enviromaster com Side Discharge Condensers 18 Dual ZONE OPERATION CHARTS...
Страница 28: ...Phone 1 800 228 9364 Fax 1 800 232 9364 5780 Success Drive Rome NY 13440...