Side Discharge Condensers

20

Single-Zone anD DUal-Zone SeqUenCe oF operation      

 

Note:

 For remote wall mounted ther

-

mostat operation be sure to select EMI 

p/n 240004180 or a suitable 24

v, two 

sage heating, heat pump thermostat. 

Condenser operation: 

The transform

-

er located in the indoor unit provides 24V, 

low-v

olt  control  power  to  the  condenser 

(outdoor  unit).  This  can  be  measured 

across low-v

olt terminals “R” and “C”.

  Single  zone  heat  pump  condensers 

utilize  a  reversing  valve  to  provide  re

-

verse cycle operation. Therefore the out

-

door unit will act as either a condenser or 

an evaporator there-by providing comfort 

cooling  or  heating  to  the  indoor  space. 

The reversing valve is energized in cool

-

ing. Should the valve fail to actuate, the 

system will default to the heating mode of 

operation.

Cooling  operation,  single-zone  and 

dual-zone: 

Cooling operation requires that 

the  control  (either  unit  mount  or  remote 

wall  mount  thermostat)  make  a  connec

-

tion  between  low-

v

olt  terminals  “R”  and 

“Y”  along  with  “R”  and  “O”  (heat  pumps 

only). When the indoor control is placed 

in  cooling  mode,  with  the  set  point  tem

-

perature below the room temperature, the 

reversing valve will energize (R & O heat 

pumps  only)  along  with  the  compressor 

and outdoor fan (R & Y). When the indoor 

control is satisfied and the room tempera

-

ture falls below the set temperature, the 

compressor and fan will de-energize. The 

anti-short cycle timer (ASCT) will prevent 

the compressor from re-starting for three 

minutes.

Heating operation

 (heat pumps only)

Heating operation requires that the con

-

trol  (either  unit  mount  or  remote  wall 

mount,  heat  pump  thermostat)  make  a 

connection  between  low-Volt  terminals 

“R” and “Y” only. When the indoor control 

is  placed  in  heating  mode,  with  the  set 

point temperature above room tempera

-

ture,  the  compressor  and  outdoor  fan 

(R  &  Y)  will  energize.  When  the  indoor 

control is satisfied and the room temper

-

ature  rises  above  the  set  temperature, 

the compressor and fan will de-energize. 

The  anti-short  cycle  timer  (ASCT)  will 

prevent the compressor from re-starting 

for three minutes.

Defrost  controls  with  short  cycle 

protection

 

(heat  pumps  only)

:

  The  unit 

is equipped with a logic control circuit de

-

signed to keep system operating at peek 

efficiency. The 24

v

 circuit provides control 

to the indoor and outdoor systems includ

-

ing a three minute, anti-short cycle timer 

(ASCT) compressor protection. 

  The defrost control circuit is designed 

to keep the condenser coil free from frost 

and ice during heating mode. This is ac

-

complished through the precise switching 

sequence  of  the  outdoor  fan,  reversing 

valve and indoor auxiliary heater.

Defrost initiation:

 The defrost-sensor 

is located on either the end plate or the re

-

turn bend of the condenser coil. A defrost 

cycle  will  initiate  after  the  sensor  closes 

(approx.  30°  F)  and  remains  closed  for 

the length of time selected on the control 

board (either 30, 60 or 90 minutes)*.

  At the start of the defrost cycle, the re

-

versing valve will change from heating to 

cooling mode. The condenser fan will also 

switch off there-by allowing pressure and 

temperature to rise within the condenser 

coil to melting off any ice build-up. At the 

same  time  the  unit  will  switch  on  the  in-

door  electric  strip  heater  to  temper  the 

cold air being discharged from the evapo

-

rator  unit.  This  will  continue  until  either 

the defrost-sensor opens (approx. 60° F) 

or a 10-minute maximum cycle time has 

elapsed. Defrost times will vary depend

-

ing on outdoor temperature and moisture 

conditions. When the defrost cycle is com

-

plete the unit will return to normal heating 

operation. 

*Factory  settings  9-24k  Btu  =  90 
minutes

W

Содержание AmericaSeries S1C2

Страница 1: ...ump S1C S1H Nominal Circuit Capacities S1C S1H 9 000 12 000 18 000 24 000 Btuh and S1C 30 36 Btuh Cooling Only S2C Nominal Circuit Capacities 9 000 12 000 Btuh Enviromaster International LLC 5780 Succ...

Страница 2: ...he same as the electric supply to the unit The EMI AmericaSeries condens ing unit must be connected only to a properly grounded electrical sup ply Do not fail to properly ground this unit Turn off the...

Страница 3: ...9 12 only Low voltage terminal connections Large capacity suction accumulator 09 12 only Solid core filter drier 09 12 only Thermostatically controlled crankcase heater 09 12 S1H s H P S High pressure...

Страница 4: ...1 Place the unit on a flat concrete surface or pad if on the ground Roof mounting should use a build up platform to avoid intake of hot air from the roof 2 In areas of heavy snowfall condens ers shou...

Страница 5: ...sor Accumulator Capacitor Filter Drier 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating 4 To access electrical connections and wiring diagram a...

Страница 6: ...he unit and into the electrical box and an chor with the strain relief fitting 7 Run wires to the high volt pigtail in the con trolboxandattachL1andL2connections Also run green wire to ground wire Hig...

Страница 7: ...Use only clean refrigeration tubing Use tube benders to guard against kinking Avoid piping on wet and rainy days and insulate suction line Be certain that plastic end caps remain in place when inserti...

Страница 8: ...r is 30 feet tall then a P trap is recommended at the 15 foot mark of the suction riser see Figure 1 AP trap may be fabricated using 2 street elbows and 2 regular elbow A prefab Installation Instructi...

Страница 9: ...tubing and insert into fittings 5 Attach manifold set 6 Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks Refrigerant Refer to Refrigerant Charge Tab...

Страница 10: ...tables starting on page 10 S1C REFRIGERANT CHARGE TABLE CONDENSER EVAPORATOR PAIRING LINE CHG FT FACTORY CHARGE S1C9 CAH12 25 oz 37 oz S1C2 CAH12 25 oz 40 oz S1C8 CAH24 56 oz 51 oz S1C4 CAH24 56 oz 65...

Страница 11: ...sures temperatures on system supplied with Low Ambient Option the fan cycle switchshouldbejumpedoutofthecircuit temporarily to obtain accurate data Installation Instructions REFRIGERANT PROCESSING co...

Страница 12: ...www enviromaster com Side Discharge Condensers 12 SINGLE ZONE OPERATION CHARTS...

Страница 13: ...www enviromaster com Side Discharge Condensers 13 SINGLE ZONE OPERATION CHARTS...

Страница 14: ...www enviromaster com Side Discharge Condensers 14 SINGLE ZONE OPERATION CHARTS...

Страница 15: ...www enviromaster com Side Discharge Condensers 15 SINGLE ZONE OPERATION CHARTS...

Страница 16: ...www enviromaster com Side Discharge Condensers 16 SINGLE ZONE Heat Pump OPERATION CHARTS...

Страница 17: ...www enviromaster com Side Discharge Condensers 17 SINGLE ZONE Heat Pump OPERATION CHARTS...

Страница 18: ...www enviromaster com Side Discharge Condensers 18 Dual ZONE OPERATION CHARTS...

Страница 19: ...ing 9 12 Btuh units if a crankcase heater is installed power the system 24 hours before attempting to start the unit in cool weather below 60 F After doing a final system check using the Operation Cha...

Страница 20: ...placed in heating mode with the set point temperature above room tempera ture the compressor and outdoor fan R Y will energize When the indoor control is satisfied and the room temper ature rises abo...

Страница 21: ...fan will switch off the re versing valve will energize and the defrost board will energize the indoor electric heat relay through the W terminal After the two second defrost cycle is complete the unit...

Страница 22: ...al Dimensions Model Size S2C A B C 99 32 15 36 22 92 32 15 40 Shipping Weight Model Size Lbs 99 129 22 167 92 157 S2C ELECTRICAL SPECIFICATIONS capacity Volts HZ Phase Fan Mtr Compressor Total AMPS MC...

Страница 23: ...f S1C9 CAH12 9 000 13 0 79 11 7 R22 S1C2 CAH12 12 000 13 0 72 12 2 R22 S1C8 CAH24 18 000 13 0 76 12 3 R22 S1C4 CAH24 23 000 13 0 67 11 8 R22 S1C3 CAC36 30 000 14 0 82 12 0 R22 S1C6 CAC36 36 000 13 0 7...

Страница 24: ...73 12 1 3 8 R22 S1H4 WLH24 23 000 20 600 13 0 8 3 71 11 9 3 5 R22 NOTE All EMI products are subject to ongoing development Design and specifications may change without notice S1C S1H Specifications a...

Страница 25: ...R22 Cooling Systems with S2C Side discharge Wall Unit s Condenser Btuh SEER SHR EER Ref WLH09 WLH09 S2C99 18 000 13 0 80 11 9 R22 WLH12 WLH12 S2C22 23 000 13 0 72 12 4 R22 WLH09 WLH12 S2C92 21 000 13...

Страница 26: ...Unit Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Ai...

Страница 27: ...Line Indoor Units outdoor Units S1C S1H Single Zone Side Discharge S2C S2H Dual Zone Side Discharge WLC WLH High Wall Air handler CAc CAH Cassette Air handler UNC UNH Universal Floor or Ceiling Air H...

Страница 28: ...Phone 1 800 228 9364 Fax 1 800 232 9364 5780 Success Drive Rome NY 13440...

Отзывы: