www.enviromaster.com
Side Discharge Condensers
11
The units are delivered precharged
with refrigerant for the condenser coil
and the evaporator. Charging of the field
installed piping is required. Refer to the
refrigerant charge table for the proper
amount to be added for the applications
interconect piping. Unit service valves are
solid brass, for sweat connections.
important:
All systems require
field charge adjustments. Refer to the
"Refrigerant Charge Tables" for proper
weight charge and to the supplied
"Operational Charts" for proper system
pressures and temperature at different
outdoor conditions. Superheat should
be used for final system charge.
When charging and checking pres-
sures/temperatures on system supplied
with low ambient option, the fan cycle
switch should be jumped out of the circuit
temporarily to obtain accurate data.
inStallation inStrUCtionS
reFrigerant proCeSSing
Continued
S2C reFrigerant CHarge table
ConDenSer
eVaporator pairing
line CHg/Ft
FaCtorY CHarge
S2C99
WLH09
.25 oz.
28 oz./ 28 oz.
S2C22
WLH12
.25 oz.
33 oz./ 33 oz.
S2C92
WLH09+WLH12
.25 oz.
28 oz./ 33 oz.
S2C99
CAC12
.25 oz.
28 oz./ 28 oz.
S2C22
CAC12
.25 oz.
33 oz./ 33 oz.
S2C92
CAC12
.25 oz.
28 oz./ 33 oz.
S2C99
UNH09
.25 oz.
28 oz./ 28 oz.
S2C22
UNH12
.25 oz.
33 oz./ 33 oz.
S2C92
UNH09+UNH12
.25 oz.
28 oz./ 33 oz.
Warning
it is illegal to discharge refrigerant
into the atmosphere. Use proper re-
claiming methods & equipment when
installing or servicing this unit.
Note: The following air handlers are equivelent in electrical specifications
and system combinations.
WLH09 = UNH09
WLH12 = WLH12
WLH24 = UNH24
WLC30 = UNC36
WLC36 = UNC36
Содержание AmericaSeries S1C2
Страница 12: ...www enviromaster com Side Discharge Condensers 12 SINGLE ZONE OPERATION CHARTS...
Страница 13: ...www enviromaster com Side Discharge Condensers 13 SINGLE ZONE OPERATION CHARTS...
Страница 14: ...www enviromaster com Side Discharge Condensers 14 SINGLE ZONE OPERATION CHARTS...
Страница 15: ...www enviromaster com Side Discharge Condensers 15 SINGLE ZONE OPERATION CHARTS...
Страница 16: ...www enviromaster com Side Discharge Condensers 16 SINGLE ZONE Heat Pump OPERATION CHARTS...
Страница 17: ...www enviromaster com Side Discharge Condensers 17 SINGLE ZONE Heat Pump OPERATION CHARTS...
Страница 18: ...www enviromaster com Side Discharge Condensers 18 Dual ZONE OPERATION CHARTS...
Страница 28: ...Phone 1 800 228 9364 Fax 1 800 232 9364 5780 Success Drive Rome NY 13440...