50 • XM678D I&O Manual
026-1219 Rev 3
CF
°F
Temperature
measurement unit
°F(1); °C(0)
°F
= Fahrenheit.
°C
= Celsius;
CAUTION! When the measurement unit
changes,
all parameters
with
temperature values
will have to be
checked
.
PrU
rE
Pressure Mode
rE(0); Ab(1)
Defines the mode to evaluate the
pressure values.
CAUTION!
PrU
value is used for all the
pressure parameters. If
[PrU = rE]
, all
pressure parameters are in relative
pressure unit, if
[PrU = Ab]
, all
pressure parameters are in absolute
pressure unit.
PMU
PSI
Pressure
measurement unit
bAr(0); PSI(1); MPA(2)
Selects the pressure measurement units.
MPA
means the value of pressure
measured by kPA*10.
PMd
PrE
Pressure probe
visualization
tEM, PrE
Selects the visualization of pressure
probe (P5):
tEM
= temperature;
PrE
= pressure
rES
dE
Resolution
(only °C)
dE; in
Sets decimal point display.
in
= 1°C;
dE
= 0.1°C.
Lod
tEr
Local display:
default display
nP(0); P1(1); P2(2);
P3(3); P4(4); P5(5);
P6(6); tEr(7); dEF(8)
Selects which probe is displayed by the
instrument.
nP
= no probe;
P1, P2, P3, P4
,
P5
,
P6
,
tEr =
virtual
probe for thermostat;
dEF =
virtual probe for defrost.
rEd
tEr
Remote display:
default display
nP(0); P1(1); P2(2);
P3(3); P4(4); P5(5);
P6(6); tEr(7); dEF(8)
It selects which probe is displayed by
the X-REP.
nP
= no probe;
P1, P2, P3, P4
,
P5
,
P6
,
tEr =
virtual
probe for thermostat;
dEF =
virtual probe for defrost.
dLY
0.0
Display delay
0.0 to 24h00min (144)
When the temperature changes, the
display is updated of 1°F/1°C when the
delay time expires.
Format
: min.10sec
Resolution
: 10sec
rPA
P1
Regulation probe A
nP(0); P1(1); P2(2);
P3(3); P4(4); P6(5)
First probe used to regulate room
temperature. If
[rPA = nP]
, the
regulation is performed with the real
value of
rPb
.
rPb
nP
Regulation probe B
nP(0); P1(1); P2(2);
P3(3); P4(4); P6(5)
Second probe used to regulate room
temperature. If
[rPb = nP]
, the
regulation is performed with the real
value of
rPA
.
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map