MODBUS Termination Blocks
Default Parameter Map • 57
i2F
LiG
Digital input 2
configuration
EAL; bAL; PAL; dor;
dEF; AUS; LiG; OnF;
Htr; FHU; ES; HdY
EAL
=
external alarm;
bAL
=
serious
external alarm;
PAL
=
pressure switch
activation;
dor
=
door open;
dEF
=
defrost activation;
AUS
=
auxiliary activation;
LiG
=
light activation;
OnF
=
switch
on/off the instrument;
Htr
=
change
type of action;
FHU
=
not used;
ES
=
activate energy saving;
HdY
=
activate holiday function.
d2d
5
Digital input 2
activation delay
0 to 255min
When
[i2F
=
PAL]
: time interval to
calculate the number of the pressure
switch activation.
When
[i2F = EAL
or
bAL]
(external
alarms):
d2d
parameter defines the time
delay between the detection and the
successive signaling of the alarm.
When
[i2F = dor]
:
this is the delay to
activate door open alarm.
i3P
CL
Digital input 3
polarity
OP; CL
CL
= the digital input is activated by
closing the contact.
OP
= the digital input is activated by
opening the contact.
i3F
ES
Digital input 3
configuration
EAL; bAL; PAL; dor;
dEF; AUS; LiG; OnF;
Htr; FHU; ES; HdY
EAL
=
external alarm;
bAL
=
serious
external alarm;
PAL
=
pressure switch
activation;
dor
=
door open;
dEF
=
defrost activation;
AUS
=
auxiliary activation;
LiG
=
light activation;
OnF
=
switch
on/off the instrument;
Htr
=
change
type of action;
FHU
=
not used;
ES
=
activate energy saving;
HdY
=
activate holiday function.
d3d
0
Digital input 3
activation delay
0 to 255min
When
[i3F
=
PAL]
: time interval to
calculate the number of the pressure
switch activation.
When
[i3F = EAL
or
bAL]
(external
alarms):
d3d
parameter defines the time
delay between the detection and the
successive signaling of the alarm.
When
[i3F = dor]
:
this is the delay to
activate door open alarm.
nPS
15
Number of pressure
switch activations
before lock
0 to 15
Number of pressure switch activation,
during the
d1d
,
d2d
and
d3d
interval,
before signaling the alarm event
[i1F,
i2F or i3F = PAL]
. If the
nPS
activation in the
d1d, d2d or d3d
time
is reached, switch off and on the
instrument to restart normal regulation.
Label
Value
Description
Range
Notes
Table 24-1