MODBUS Termination Blocks
Default Parameter Map • 51
rPE
100
Virtual probe
percentage
(room temperature)
0 to 100%
Defines the percentage of the
rPA
with
respect to
rPb
. The value used to
regulate the room temperature is
obtained by:
value_for_room = (rPA*rPE +
rPb*(100-rPE))/100
DEFROST
dPA
P2
Defrost probe A
nP(0); P1(1); P2(2);
P3(3); P4(4); P6(5)
First probe used for defrost. If
[dPA = nP]
, the regulation is performed
by time.
dPb
nP
Defrost probe B
nP(0) - P1(1) - P2(2) -
P3(3) - P4(4) - P5(5)
Second probe used for defrost. If
[dPb = nP]
, the regulation is performed
with
dPA
.
dPE
100
Percentage of the
first defrost probe
0 to 100
(100=dPA, 0=dPb)
Defines the percentage of the
dPA
with
respect to
dPb
. The value used to
regulate room temperature is obtained
by:
value_for_defrost= (dPA*dPE +
dPb*(100-dPE))/100
tdF
EL
Defrost kind
EL; in
EL
= defrost with electrical heater
in
= hot gas defrost
NOTE: The valve opening percentage
during the defrost is set by the
parameter oPd.
Srt
302
Heater setpoint
during defrost
[-67°F to 302°F]
[-55.0°C to 150°C]
If
tdF=EL
during the defrost the defrost
relay perform an ON/OFF regulation
with
Srt
as set point.
Hyr
4
Differential for
heater
[1°F to 45°F]
[0.1°C to 25.5°C]
If the defrost probe temperature is
bigger than
Srt
for all
tod
time, the
defrost ends although the defrost probe
temperature is lower than
dtE
or
dtS
. It
permits to reduce defrost duration.
tod
255
Time out for heater
0 to 255min
If the difference between the two
defrost probes stays lower than
dtP
for
all
ddP
time the defrost is activated;
dP2
n
Defrost with two
probes
n(0) – Y(1)
n
= only the
dPA
probe is used to
defrost management;
Y
= defrost is
managed with
dPA
probe and
dPb
probe. Defrost can performed only if
both probe value are lower than
dtE
for
dPA
probe and
dtS
for
dPb
probe
dtE
46
End defrost
temperature on
probe A (
dPA
)
[-67°F to 122°F]
[-55.0°C to 50.0°C]
Set the temperature measured by the
evaporator probe
dPA
which stops the
defrost.
Parameter enabled only when
the evaporator probe is present.
dtS
46
Defrost termination
temperature
(Probe B)
[-67°F to 122°F]
[-55.0°C to 50.0°C]
(Enabled only when the evaporator
probe is present) Sets the temperature
measured by the evaporator probe
dPb
resulting to end of defrost.
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map