Alarm Recovery
Display Messages • 31
17.1.Alarm Recovery
Probe alarms
P1
,
P2
,
P3
, and
P4
start some seconds
after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal
operation. Check the connections before replacing the
probe.
Temperature alarms
HA
,
LA
,
HA2
, and
LA2
automatically stop as soon as the temperature returns
to normal values.
Alarms
EA
and
CA
(with
i1F
=
bAL
) recover as soon
as the digital input is disabled. Alarm
CA
(with
i1F
=
PAL
) recovers only by switching OFF and ON
the device.
17
PAL
Pressure switch lock
i1F
,
i2F
o
i3F
=
PAL
.
All the outputs are OFF.
ELECTRONIC VALVE ALARM
18
LOP
Minimum operating pressure threshold from
LOP
parameter.
The valve output increases its opening of
dML
quantity every second.
19
MOP
Maximum operating pressure threshold from
MOP parameter.
The valve output decreases its opening of
dML
quantity every second.
20
LSH
Low superheating from
LSH
parameter and
SHd
delay.
The valve will be closed; the alarm will be
showed after
SHd
delay.
21
HSH
High superheating from
HSH
parameter and
SHd
delay.
Only display.
CLOCK ALARM
22
rtC
Clock settings lost.
Defrost will be performed with
IdF
till restoring
the settings of RTC.
23
rtF
Clock damaged.
Defrost will be performed with
IdF
.
OTHERS
24
EE
EEPROM serious problem.
Output OFF.
25
Err
Error with upload/download parameters.
Repeat the operation.
26
End
Parameters have been correctly transferred.
Display
Causes
Notes
Table 17-1
- Display Messages