5. Set the
Temp Ctrl Strat
property to
MONITOR/DEFROST
.
6. Press
to go the Setpoints tab. Change
the setpoint value to the desired setpoint the
device will use. This setpoint will pass its
setting to the device after connecting inputs/
outputs.
7. Advanced to the Defrost tab and change the
defrost settings. The defrost settings must
match the device defrost settings.
8. In the Defrost tab, select the property
Term
Type
. Press
(LOOK UP)
and choose
THERMOSTAT
.
9. This will expose a digital input in the Inputs
tab to route the XM670K_50 Device
Application property
DEFROST END
, which
will be the standard circuit indication to
terminate the circuit defrost, updating the
circuit status.
10. Press
to advance to the
Defr Times
tab
and set the times.
11. The circuit will provide the Start Defrost
signal to the XM670K_50; however, the
XM670K_50 will take over all defrost
sequencing until it has ended and signal back
to the circuit to terminate defrost and update
status.
Figure 26 - Temp Ctrl Strat Property
Figure 27 - Setpoints Tab
Figure 28 - Term Type (Standard Circuits)
Figure 29 - Defrost Tab (Standard Circuits)