DOOR ALM
RESTAR
rrd
- Ref restart with door
open
If either Digital Input 1 or Digital Input 2 or Digital Input 3 is configured for
the Door Switch and after the respective digital input delay setting has
exceeded its time setting, the door alarm will be generated. The door
switch, when active, can also turn OFF the refrigeration and fan relays if
configured to do so at E2 property
Door Sw Mode
(
odC
). At the time the
alarm is generated, the loads, if configured to be OFF when a door
opening is activated,
this setting will also reactivate the loads to their normal
operating mode
.
Tmp 1 Alrm Probe
rAL
- 1st Probe used for
alarm
Selects the first probe the device will use for temperature alarming
purposes. Selecting no probe will disable this input and will display
0
on
the Status screen.
Tmp1 Alarm Hi
ALU
- High temperature
alarm 1 setting
When this temperature is reached, the alarm will turn ON only after the
TMP1 ALARM DLY (ALd)
delay time. This setting is influenced by how the
TEMP ALRM CFG (ALC)
is configured.
Tmp2 Alarm Lo
ALL
- Low temperature
alarm 1 setting
When this temperature is reached, the alarm will turn ON only after the
TMP1 ALARM DLY (ALd)
delay time. This setting is influenced by how the
TEMP ALRM CFG (ALC)
is configured.
Defrost Type
tdF
- Defrost Type
Sets the defrost action during defrost. Electric defrost will turn
refrigeration relay OFF and defrost output ON when all settings and
thresholds have been met. When
Hot Gas Defrost
is selected, the
refrigeration relay will remain on.
Defr St Delay
dSd
= Defrost Start Delay Sets the delay to start a defrost if E2 property
DEFROST MODE (Edf)
set to
Interval and E2 property
DEFR INTERVAL (idf)
set to1 hour or more.
0
=
disabled.
Fan During Defr
FnC
= Fan operating mode
during defrost
Sets the behavior of the fan relay output during defrost.
Fan Delay Defr
Fnd
= Fan delay after
defrost
Sets the behavior of the fan relay output to turn ON after defrost by
delaying the fan ON by this time setting.
0
= disabled.
IMPORTANT
: If the drip time is set above 0, add the drip time
and the delay of fan time desired to set the fan ON time to a delayed time
after drip.
Fan Probe Defr
FAP
= Probe Selection for
Fan Defr seque
Selects the evaporator coil temperature probe to allow the fan relay
output to turn ON only after a fall in temperature to below E2 property
FAN CUTIN TEMP (FHy)
, or go OFF above E2 property
FAN CUTOUT TEMP
(FSt)
. This setting along with settings
FAN CUTIN TEMP (FHy)
and
FAN
CUTOUT TEMP (FSt)
can be considered to work much like a fan
temperature thermostat would work typically found in electric defrost
applications.
Fan Cutout Temp
FSt
- Fan stop evap
temperature
Selects the temperature at which above this setting, the evaporator fan
relay output will turn OFF. This setting and E2 property
FAN PROBE DEFR
(FAP)
can be considered to work much like a fan temperature thermostat
would work typically found on electric defrost applications.
Fan Cutin Temp
Fhy
- Fan stop hysteresis
Selects the temperature at which below this setting, the evaporator fan
relay output will turn off. This setting and E2 property
FAN PROBE DEFR
(FAP
) can be considered to work much like a fan temperature thermostat
would work typically found on electric defrost applications.
Defr Term Probe
dPA
- Defrost probe
Selects which probe to use for defrost termination.
Table 2 - XM670K_50 Property Help Explanations