B - 13
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Appendix B
•
Vission 20/20 Application Procedures
The master compressor controls the slave compressors
based on the master compressor control setpoints as
well as the setpoints entered in the master compressor
sequencing menu. Page 1 of the master compressor
sequencing menu (see Figure B-8) allows the operator
to view and adjust settings which are used for compres-
sor sequencing. The pressure / temperature control set-
points and capacity load / unload timers to accomplish
sequencing control are de
fi
ned here:
1. Load Rate 2 Offset (Outer)
2. Load Rate 1 Offset (Inner)
3. Suction Pressure / Process Temperature Control
Setpoint
4. Unload Rate 1 Offset (Inner)
5. Unload Rate 2 Offset (Outer)
Load Rate 2 Offset (Outer)
• De
fi
nes the outer pressure/temperature setpoint
offset to monitor compressor load. If suction pres-
sure / process temperature surpasses the control
se load rate 1 offset and goes beyond the
control se load rate 2 offset then sequencing
decisions are made according to load rate 2 timer.
Load Rate 1 Offset (Inner)
• De
fi
nes the inner pressure/temp setpoint offset to
monitor compressor load. If suction pressure / proc
temp surpasses the Control Se load rate 1
offset then sequencing decisions are made accord-
ing to load rate 1 timer.
Suction Pressure /Process Temperature Control Setpoint
• The target setpoints are read only values here.
These setpoints can be changed by logging on
to “Compressor Control” menu of the Master
Compressor.
Unload rate 1 offset (Inner)
• De
fi
nes the inner pressure setpoint to monitor com-
pressor unload. If suction pressure / proc temp goes
below the Control Setpoint minus the unload rate 1
offset then sequencing decisions are made accord-
ing to unload rate 1 timer.
Figure B-8. Slave Compressor(s) Loading and Unloading Setup
Содержание Vission 20/20
Страница 1: ...Vission 20 20 micro controller Operation and service manual Version 2 0 ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 66: ...8 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 76: ...10 8 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 86: ...12 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 106: ...15 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 1 9 ...
Страница 108: ...16 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 136: ...21 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 146: ...24 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 154: ...26 4 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 156: ...A 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 158: ...B 2 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 162: ...B 6 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 180: ...B 24 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 204: ...B 48 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 220: ...B 64 Blank Vission 20 20 Operation and Service Manual Vilter Emerson 35391SC 2 0 ...
Страница 257: ......