69
Process Temperature Control Group
The
P
ROCESS
T
EMPERATURE
C
ONTROL
G
ROUP
screen is used to set-up the Process Temperature control
parameters when the Process Temperature Control option is enabled.
TERM
DEFINITION
RANGE
CUT-IN
Cut-in Setpoint. If Automatic or Auto-Remote mode is selected,
Auto Start/Stop is enabled, the compressor is on-line, and the process
temperature rises above the Cut-in Setpoint, the compressor will start.
-58: 122 DEGF
CONTROL
Control Setpoint. In the Automatic or Auto-Remote mode of operation
the compressor is loaded or unloaded as required to maintain the Control
Set-point.
-58: 122 DEGF
CUT-OUT
Cut-out Setpoint. If Automatic or Auto-Remote mode is selected, Auto
Start/Stop is enabled, the compressor is running, and the process temperature
falls below the Cut-out Setpoint, the compressor will stop.
-58: 122 DEGF
LOW ALARM
An alarm is reported when the Process Temperature falls below the low
alarm setpoint.
-58: 122 DEGF
LOW FAILURE
A failure is reported and the compressor is shutdown when the Process\
Temperature falls below the low failure setpoint.
-58: 122 DEGF
Process Temperature Definitions
Process Temperature Control Group
Содержание Vilter VilTech
Страница 1: ...VILTech micro controller Operation and service manual ...
Страница 2: ...2 ...
Страница 10: ...10 Notes Page ...
Страница 11: ...11 ...
Страница 16: ...16 ...
Страница 18: ...18 ...
Страница 29: ...29 ...
Страница 38: ...38 ...
Страница 53: ...53 ...
Страница 88: ...88 ...
Страница 138: ...138 ...
Страница 142: ...142 ...
Страница 145: ...145 ...
Страница 147: ...147 ...
Страница 153: ...153 ...
Страница 154: ...154 Alarm and Failure Data ...
Страница 155: ...155 Alarm and Failure Data Continued ...
Страница 156: ...156 Alarm and Failure Data Continued ...
Страница 158: ...158 Compressor State Table ...
Страница 159: ...159 Last RECIPStart Status Table ...
Страница 172: ...172 ...
Страница 173: ......