50
Setpoint Scheduling
S
ETPOINT
S
CHEDULING
is the automatic switching of Suction Pressure or Process Temperature control
setpoint groups based on time of the day and day of the week. The operator can define up to seven (7)
different daily time schedules and one weekly schedule. Schedule events can be manually overridden
and scheduling can be enabled or disabled by the operator. Setup of schedules and control of the
scheduling is performed from the Scheduling menu under the
SETPT
hot key.
Daily Schedules
Each
D
AILY
S
CHEDULE
consists of up to eight (8) different time-of-day slots. For each time-of-day
slot the operator can define the time (either in 12 or 24 hour mode, depending on system clock mode
selected) and the desired setpoint group number. Unused time slots are ignored and the schedule
may be entered in any order. When the schedule is saved it is reordered chronologically. Each daily
schedule is identified by a schedule name (SCH1 - SCH7).
Weekly Schedule
The
W
EEKLY
S
CHEDULE
allows the operator to assign different daily schedules to each day of the
week. A new day begins and schedules change at midnight. The current daily schedule or control
group may be overridden by the operator at anytime. Any item which has been manually overridden
will be changed when the next schedule change occurs.
Oil Pressure Computation
The oil pressure for a RECIP compressor is computed as follows:
Oil Pressure = Oil Pressure Sensor - Suction Pressure
The actual sensor value can be viewed on the Calibration and View analog screens. All other screens
display the computed value.
Oil Temperature Regulation
The
O
IL
T
EMPERATURE
in the crankcase is regulated when the RECIP compressor is stopped. The temperature is
maintained above the oil heater setpoint with a deadband of +5 degrees. When the compressor is stopped, and
the Oil Temperature falls below the Heater Control Setpoint, the Oil Heaters will be turned on. When the Oil
Temperature rises 5 degrees above the Heater Control setpoint, the oil heaters will be turned off. The Heater
Control Set-point may be found on the Oil Temperature Setpoints screen under the
SETPT
hot key.
Содержание Vilter VilTech
Страница 1: ...VILTech micro controller Operation and service manual ...
Страница 2: ...2 ...
Страница 10: ...10 Notes Page ...
Страница 11: ...11 ...
Страница 16: ...16 ...
Страница 18: ...18 ...
Страница 29: ...29 ...
Страница 38: ...38 ...
Страница 53: ...53 ...
Страница 88: ...88 ...
Страница 138: ...138 ...
Страница 142: ...142 ...
Страница 145: ...145 ...
Страница 147: ...147 ...
Страница 153: ...153 ...
Страница 154: ...154 Alarm and Failure Data ...
Страница 155: ...155 Alarm and Failure Data Continued ...
Страница 156: ...156 Alarm and Failure Data Continued ...
Страница 158: ...158 Compressor State Table ...
Страница 159: ...159 Last RECIPStart Status Table ...
Страница 172: ...172 ...
Страница 173: ......