Oil Temperature Setpoints
The
O
IL
T
EMPERATURE
S
ETPOINTS
screen allows the operator to set acceptable ranges for the
RECIP oil temperature.
The following table lists the data entry fields and a description of their purposes.
TERM
DEFINITION
RANGE
HIGH FAILURE
The compressor will be failed (stopped) when
the oil temperature exceeds this value.
32 - 392 DEGF
HIGH ALARM
The Viltech will report an alarm to the operator
when the oil temperature exceeds this value
32 - 392 DEGF
HEATER CONTROL
The temperature at which to maintain the oil in
the separator. The oil heater uses the Oil
Temperature sensor but only when the compressor
is stopped.
32 - 392 DEGF
LOW ALARM
The Viltech will report an alarm to the operator when
the Oil Temperature is below this value.
32 - 392 DEGF
LOW FAILURE
The compressor will be failed (stopped) when the
Oil Temperature is below this value.
32 - 392 DEGF
Oil Temperature Setpoints Screen
Oil Temperature Definitions
Содержание Vilter VilTech
Страница 1: ...VILTech micro controller Operation and service manual ...
Страница 2: ...2 ...
Страница 10: ...10 Notes Page ...
Страница 11: ...11 ...
Страница 16: ...16 ...
Страница 18: ...18 ...
Страница 29: ...29 ...
Страница 38: ...38 ...
Страница 53: ...53 ...
Страница 88: ...88 ...
Страница 138: ...138 ...
Страница 142: ...142 ...
Страница 145: ...145 ...
Страница 147: ...147 ...
Страница 153: ...153 ...
Страница 154: ...154 Alarm and Failure Data ...
Страница 155: ...155 Alarm and Failure Data Continued ...
Страница 156: ...156 Alarm and Failure Data Continued ...
Страница 158: ...158 Compressor State Table ...
Страница 159: ...159 Last RECIPStart Status Table ...
Страница 172: ...172 ...
Страница 173: ......