124
Unidrive M / Unidrive HS Modular Installation Guide
Issue Number: 5
6.16 M70X/HS7X Position feedback
connections
The following functions are provided via the 15-way high density D-type
connector on the drive:
•
Two position feedback interfaces (P1 and P2).
•
One encoder simulation output.
•
Two freeze trigger inputs (marker inputs).
•
One thermistor input.
The P1 position interface is always available but the availability of the P2
position interface and the encoder simulation output depends on the
position feedback device used on the P1 position interface, as shown in
Table 6-29.
6.16.1 Location of position feedback connector
Figure 6-42 Location of the position feedback
11
Safe Torque Off function input 1 (drive enable)
13
Safe Torque Off function input 2 (drive enable)
Type
Positive logic only digital input
Voltage range
0V to +24 V
Absolute maximum applied
voltage
30 V
Logic Threshold
10 V ± 5 V
Low state maximum voltage for
disable to SIL3 and PL e
5 V
Impedance
>4 mA @15 V (IEC 61131-2, type 1, 3.3 k
Ω)
Low state maximum current for
disable to SIL3 and PL e
0.5 mA
Response time
Nominal: 8 ms
Maximum: 20 ms
The Safe Torque Off function may be used in a safety-related application in
preventing the drive from generating torque in the motor to a high level of
integrity. The system designer is responsible for ensuring that the complete
system is safe and designed correctly according to the relevant safety
standards. If the Safe Torque Off function is not required, these terminals are
used for enabling the drive.
41
Relay contacts
42
Default function
Drive healthy indicator
Contact voltage rating
240 Vac, Installation over-voltage
category II
Contact maximum current rating
2 A AC 240 V
4 A DC 30 V resistive load
0.5 A DC 30 V inductive load (L/R = 40 ms)
Contact minimum recommended
rating
12 V 100 mA
Contact type
Normally open
Default contact condition
Closed when power applied and drive
healthy
Update period
4 ms
51
0V common
52
+24 Vdc
Size 9 to 11
Nominal operating voltage
24.0 Vdc
Minimum continuous operating voltage
19.2 Vdc
Maximum continuous operating voltage
30 Vdc (IEC),
26 Vdc (UL)
Minimum startup voltage
21.6 Vdc
Maximum power supply requirement
60 W
Recommended fuse
4 A @ 50 Vdc
To prevent the risk of a fire hazard in the event of a fault, a
fuse or other over-current protection must be installed in the
relay circuit.
WARNING
WARNING
5
10
15
1
6
11
Drive encoder connector
Female 15-way D-type