7.1.10 Corrosive gasses
Concentrations of corrosive gases must not exceed the levels given in:
•
Table A2 of EN 50178:1998
•
Class 3C2 of IEC 60721-3-3
This corresponds to the levels typical of urban areas with industrial
activities and/or heavy traffic, but not in the immediate neighborhood of
industrial sources with chemical emissions.
7.1.11 RoHS compliance
The drive meets EU directive 2011/65/EU for RoHS compliance.
7.1.12 Vibration
Maximum recommended continuous vibration level 0.14 g r.m.s. broad-
band 5 to 200 Hz.
This is the limit for broad-band (random) vibration. Narrow-band
vibration at this level which coincides with a structural resonance could
result in premature failure.
Bump Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard:IEC 60068-2-29: Test Eb:
Severity: 18 g, 6 ms, half sine
No. of Bumps: 600 (100 in each direction of each axis)
Random Vibration Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard:IEC 60068-2-64: Test Fh:
Severity: 1.0 m²/s³ (0.01 g²/Hz) ASD from 5 to 20 Hz
-3 dB/octave from 20 to 200 Hz
Duration: 30 minutes in each of 3 mutually perpendicular axes.
Sinusoidal Vibration Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard: IEC 60068-2-6: Test Fc:
Frequency range: 5 to 500 Hz
Severity: 3.5 mm peak displacement from 5 to 9 Hz
10 m/s² peak acceleration from 9 to 200 Hz
15 m/s² peak acceleration from 200 to 500 Hz
Sweep rate: 1 octave/minute
Duration: 15 minutes in each of 3 mutually perpendicular axes.
EN 61800-5-1:2007, Section 5.2.6.4. referring to IEC 60068-2-6
Frequency range: 10 to 150 Hz
Amplitude: 10 to 57 Hz at 0.075 mm pk
57 to 150 Hz at 1g p
Sweep rate: 1 octave/minute
Duration: 10 sweep cycles per axis in each of 3 mutually
perpendicular axes
7.1.13 Starts per hour
By electronic control: unlimited
By interrupting the AC supply:
≤
20 (equally spaced)
7.1.14 Start up time
This is the time taken from the moment of applying power to the drive, to
the drive being ready to run the motor:
Size 9 to 11: 5s
7.1.15 Output frequency / speed range
Unidrive Mxxx
models:
In all operating modes (Open loop, RFC-A, RFC-S) the maximum output
frequency is limited to 550 Hz.
Unidrive HSxx
models:
In open loop mode the maximum achievable output frequency is 3,000
Hz.
In RFC-A and RFC-S modes, the maximum achievable output frequency
is 1,250Hz.
In RFC-S mode the speed is also limited by the voltage constant (Ke) of
the motor unless field weakening operation is enabled. Ke is a specific
constant for the servo motor being used. It can normally be found on the
motor data sheet in V/k rpm (volts per 1,000 rpm).
It is recommended that a minimum ratio of 12:1 is maintained between
the switching frequency and the maximum output frequency to maintain
the quality of the output waveform. If this minimum ratio is exceeded,
extra motor losses will result due to the increased harmonic content of
the output waveform.
7.1.16 Accuracy and resolution
Speed:
The absolute frequency and speed accuracy depends on the accuracy
of the crystal used with the drive microprocessor. The accuracy of the
crystal is 100 ppm, and so the absolute frequency/speed accuracy is
100 ppm (0.01 %) of the reference, when a preset speed is used. If an
analog input is used the absolute accuracy is further limited by the
absolute accuracy of the analog input.
The following data applies to the drive only; it does not include the
performance of the source of the control signals.
Open loop resolution:
Preset frequency reference: 0.1 Hz
Precision frequency reference: 0.001 Hz
Closed loop resolution
Preset speed reference: 0.1 rpm
Precision speed reference: 0.001 rpm
Analog input 1: 11 bit plus sign
Analog input 2: 11 bit plus sign
Current:
The resolution of the current feedback is 10 bit plus sign.
Accuracy: typical 2 %
worst case 5 %
7.1.17 Acoustic noise
The heatsink fan generates the majority of the sound pressure level at 1 m
produced by the drive. The heatsink fan on size 9, 10 and 11 is a variable
speed fan. The drive controls the speed at which the fan runs based on
the temperature of the heatsink and the drive's thermal model system.
Table 7-17 gives the sound pressure level at 1 m produced by the drive for
the heatsink fan running at the maximum and minimum speeds.
Table 7-17 Acoustic noise data
NOTE
Size
Max speed
dBA
Min speed
dBA
9A/9E/9T/10E/10T
75.0
52.6
9D/10D
77.1
53.8
9/10 rectifier
67.1
40.7
11E/11T
82.5
58
11D
79.5
60.4
11 rectifier (single or twin)
66.5
44.8