BYTE8 bit 0 is line fail (1 = INV, 0 = LINE)
bit 1 is low battery (1 = BAt LoW, 0 = noRMAL)
bit 2 reserved
bit 3 AVR (1 = AVR, 0 = no AVR)
bit 4 AVR MoDe (1 = Boost, 0 = BUCK)
bit 5 LoAD stAtUs(1 = oVeR LoAD, 0 = noRMAL)
bit 6 reserved
bit 7 sD MoDe DIsPLAY
BYTE9 bit 0 reserved
bit 1 BAt stAtUs(1 = BAD, 0 = noRAML)
bit 2 test MoDe (1 = test, 0, noRMAL)
bit 3 Buzzer silence on/off (1=sILenCe)
Buzzer silence off = Alarm enabled
Buzzer silence on = Alarm Disabled
bit 4 PRe-sD CoUnt MoDe (1 = ACtIVe)
bit 5 sCHeDULe CoUnt MoDe (1 = ACtIVe)
bit 6 DIsBLe no LoAD sHUtDoWn (1 = ACtIVe)
bit 7 reserved
BYTE10
UPS model number
32H =500VA 120V
39H =500VA 230V
52H =850VA 120V
59H =850VA 230V
BYTE11 UPS PRE-SD COUNT TIME MIN
BYTE12
UPS PRE-SD COUNT TIME SEC
BYTE13,14 UPS PRE-ON COUNT TIME
BYTE15 UPS FIRMWARE Ver
Output (8 Bytes):
the command Instance is mapped to output message structure is the same as outlined in the command instance chapter.
6.3 Web Server
sDU device has a web server that can be accessed via most browsers that can be used to both monitor and configure the UPs.
Instructions:
to use the web server, enter the IP address in your URL bar.
Figure 14. Web Server Window Example
sDU AC - A seRIes CoMM CARDs InstRUCtIon MAnUAL |
19