3.1 Identification
each Protocol has different parameters for identifying the sDU on the network. the following section will specify how the sDU will be
identified on each network. It is organized by the instance attribute number of the corresponding Host object. the sDU must respond
to requests with highlighted values. For default value it will suffice for response with error response- indicated by Respond with error.
For Respond with error, it is not required to specify type.
Attr #
Name
Datatype Response
Response Value
EtherNet/IP - SDUENETIPCARD (object 0xF8)
1
Vendor ID (from oDVA )
UInt16
1181
2
Device type
UInt16
Respond with error
3
Product Code
UInt16
2
4
software Revision
struct of {UIn8 , UInt8}
1.03
5
serial number
UInt32
Respond with error
6
Product name
Array of CHAR
sDU Industrial UPs
EtherCAT - SDUECATCARD
(object 0xF5)
1
Vendor ID (from etG* )
UInt32
0x00000906
2
Product Code
UInt32
1F4
3
Major Rev
UInt16
1
4
Minor Rev
UInt16
03
5
serial number
UInt32
Respond with error
6
MFG Device name
Array of CHAR (max 64 )
sDU Industrial UPs
PROFINET - SDUPNETCARD (object 0xF6)
1
Device ID**
UInt16
1F4
2
Vendor ID (from Pno*)**
UInt16
Respond with error
3
station type**
Array of CHAR
sDU Industrial UPs
8
I&M order**
Array of CHAR
sDU Industrial UPs
9
I&M serial number
Array of CHAR
Respond with error
19
system Description
Array of CHAR
sDU Industrial UPs
Modbus Host (object 0xFA)
1
Vendor name
Array of CHAR
soLA HD
2
Product Code***
Array of CHAR
sDU Industrial UPs
3
Major Minor Rev***
Array of CHAR
1.03
4
Vendor URL
Array of CHAR
www.solaHD.com
5
Product name
Array of CHAR
sDU Industrial UPs
6
Model name
Array of CHAR
sDU Industrial UPs
7
User Application name
Array of CHAR
Respond with error
* PNO = PROFINET User Organization
** Entries must match the information located in the GSDML device File
*** Used IPCONFIG tool.
Table 7. Network Identifications
sDU AC - A seRIes CoMM CARDs InstRUCtIon MAnUAL |